SiE33-003
Test Operation
General Information
85
BRC7C Type
Group No. setting by infrared remote control for centralized control
1. When in the normal mode, push
button for 4 seconds or more, and operation then enters the
“field set mode.”
2. Set mode No. “00” with
button.
3. Set the group No. for each group with
button (advance/backward).
4. Enter the selected group numbers by pushing
button.
5. Push
button and return to the normal mode.
BRC7C Type
Group No. Setting
Example
If you have to set the address for each unit for calculating cost, etc., set the mode No. to “30.”
Caution
When turning the power supply on, the unit may ofen not accept any operation while "88" is displaying after
all indications were displayed once for about 1 minute on the liquid crystal display.
This is not an operative fault.
Central Remote
Control
F1 F2
F1 F2
F1 F2
F1 F2
P1 P2
RC
RC
RC
RC
RC
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
No Remote Control
Group Control by Remote Contol
(autmatic unit address)
1-03
1-00
1-01
Main
Sub
1-02
1-04
Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2
Indoor/Outdoor Outdoor/Outdoor
(V0917)
Si33-003.book Page 85 Monday, June 25, 2001 9:06 AM