7.4
Power Circuit and Cable Requirements
A power circuit (See table below) must be provided for connection of the unit. This circuit must be protected
with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leak
detector.
When using residual current operated circuit breakers, be sure to use a high-speed type 200mA rated
residual operating current.
Note:
Select the power supply cable in accordance with relevant local and national regulations.
Phase and
Frequency
Voltage
Recommended
Fuses
Transmission
Line Selection
RSXYP16
3N~50Hz
380-415V
45A
0.75-1.25mm
²
RSXYP18
3N~50Hz
380-415V
50A
0.75-1.25mm
²
RSXYP20
3N~50Hz
380-415V
60A
0.75-1.25mm
²
RSXYP24
3N~50Hz
380-415V
60A
0.75-1.25mm
²
RSXYP26
3N~50Hz
380-415V
70A
0.75-1.25mm
²
RSXYP28
3N~50Hz
380-415V
70A
0.75-1.25mm
²
RSXYP30
3N~50Hz
380-415V
70A
0.75-1.25mm
²