Test Operation
SiE33-003
66
General Information
4.4.3
Monitor Mode
After making sure the data is correct, push the RETURN button and return to No. 0, or push the
MODE button and return to setting mode 1.
16
4
32
8
2
1
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
MODE
To enter the monitor mode, push the MODE button when in setting mode 1.
RETURN
SET
SET
SET
The lower 4 digits indicate the setting in each of the frames
below.
The No. 1 cool/heat group address is expressed as a
binary number consisting of the lower 6 digits. (0 - 63)
In (1), the address is 010110 (binary number), which
translates to 16 + 4 + 2 = 22 (base 10 number). In other
words, the address is 22.
Tc (high pressure for heating)
High
Normal (factory set)
Low
Te (low pressure for cooling)
High
Normal (factory set)
Low
Defrost
(temperature setting for defrost)
Quick defrost
Normal (factory set)
Slow defrost
EMG
(emergency operation when
malfunction occurs)
ON
OF
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button,
and enter the data for each setting.
* Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
∗
See the following page for a list of the data for No. 1 - 16.
1
The number of terminal blocks for No. 12 and 13 is
expressed as an 8-digit binary number which is the
combination of four upper and four lower digits for No.
12 and 13 respectively. (0 - 128)
In (2), the address for No. 12 is 0101, the address for
No. 13 is 0110, and the combination of the two is
01010110 (binary number), which translates to 64 + 16
+ 4 + 2 = 86 (base 10 number). In other words, the
number of terminal blocks is 86.
64
16
No12
128
32
2
4
1
No13
8
2
No 0
RETURN
No 1
No 16
RETURN
(1 to 15 times)
C/H SELECT
(V1331)
Si33-003.book Page 66 Monday, June 25, 2001 9:06 AM