Refrigerant Piping
SiE33-003
138
Installation Manual
6.3
Connecting the Refrigerant Piping
1. Piping
Installation
Installation of refrigerant piping is possible as front connection, side connection and bottom connection.
Caution
Be sure to use the attached pipe when carrying out piping work in the field.
Separately use the optional “KHF30A30L” or “KHF30A30U” piping kit when carrying out connections for
the side and bottom on RSXYP24, 26, 28, and 30.
Connect the flange on the valve on the gas side before connecting the flare nut on the valve on the
liquid side.
(Connecting the liquid side first will make it harder to connect the gas side.)
Be sure that the local piping does not touch other pipes, the bottom panel or side panel. Especially
for the bottom and side connection, be sure to protect the gas piping with the provided insulation,
to prevent it from coming into contact with the casing.
Notes:
1. Front Connection
Make sure to close the piping intake hole again after installation work.
Stop valve cover
2. Side Connection
Use a hammer and knock out the hole.
Piping kit “KHF30A30L” is required for RSXYP24,26,28 and 30.
Refer the optional “KHF30A30L” or “KHF30A30U” piping kit on page 104 for more detail.
1. Flange
2. Flare nut
3. Gas side attached pipe
4. Gas side optional pipe
5. Liquid side attached pipe
(Field supply, in case of
RSXYP24)
6. Liquid side optional pipe
(Field supply, in case of
RSXYP24)
7. Gas side pipe (Field supply)
8. Liquid side pipe
(Field supply)
9. Elbow (Field supply)
10.Brazing
11.Knock out hole
(use a hammer)
1
8
10
3
2
RSXYP16,18,20
1
8
2
11
10
3
7
1
2
9
8
11
10
3
7
1
2
3
5
RSXYP24,26,28,30
10
10
11
2
4
4
6
6
1
1
4
4
2
6
10
11
Fig. 6
(V0854)
1. Part to cut off (Cut off the slit part.)
2. Part to cut off (Cut grooves on the back side.)
RSXYP16,18,20
1
RSXYP24,26,28,30
2
Fig. 7
(V0855)