Installation manual

15

ERSQ+ERRQ011~Y1

Outdoor unit for air to water heat pump

4PW49635-1A

10. S

TART

-

UP

 

AND

 

CONFIGURATION

10.1. Pre-operation checks

After the installation, check the following before switching on the
circuit breaker:

1

Transportation stay
Be sure that the transportation stay is removed from the
compressor.

2

Power supply wiring and transmission wiring
Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.

3

Pipe sizes and pipe insulation
Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.

4

Additional refrigerant charge
The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.

5

Insulation test of the main power circuit
Using a megatester for 500 

V, check that the insulation

resistance of 2 M

 or more is attained by applying a voltage of

500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring.

6

Stop valves
Be sure that the stop valves are open on both liquid and gas
side.

11. T

EST

 

OPERATION

 

AND

 

FINAL

 

CHECK

11.1. Final check

Be sure to perform a test run.

To  protect the compressor, make sure to turn on the power
supply 6 hours before starting operation.

Be sure to fully open the liquid-side and gas-side stop valves. If
you operate the unit with stop valves closed, the compressor will
break down.

Never leave the unit unattended with an open front panel during
test run.

After installation, perform the test operation.
Unless the test operation is performed, the error code "

U3

" is

shown on the remote controller and the unit cannot be operated.

During tests never pressurize the appliances with a pressure
higher than the maximum allowable pressure (as indicated on
the nameplate of the unit).

Provide a logbook.
In accordance with the relevant national and international
regulations it may be neccesary to provide a logbook with the
equipment containing at least:
-

info on maintenance,

-

repair work,

-

results of tests,

-

stand-by periods,

-

...

In Europe, EN378 provides the neccesary guidance for this
logbook.

11.2. Test run

Perform the test run in accordance with the indoor installation manual
to ensure that all functions and parts are working properly.

Make sure that the circuit breaker on the power supply
panel of the installation is switched off.

Attach the power wire securely.

Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.

Items to check

Electrical wiring
Inter-unit wiring
Earth wire

Is the wiring as mentioned on the wiring diagram?
Make sure no wiring has been forgotten and that
there are no missing phases or reverse phases.

Is the unit properly earthed?

Is the wiring between units connected in series
correct?

Are any of the wiring attachment screws loose?

Is the insulation resistance at least 1 M

?

-

Use a 500 V mega-tester when measuring 
insulation.

-

Do not use a mega-tester for low-voltage circuits.

Refrigerant 
piping

Is the size of the piping appropriate?

Is the insulation material for the piping attached
securely?
Are both the liquid and gas pipes insulated?

Are the stop valves for both the liquid side and the
gas side open?

Extra 
refrigerant

Did you write down the extra refrigerant and the
refrigerant piping length?

NOTE

After turning on the power supply, the unit can not be
started until the H2P initialisation led goes off
(maximum 12 minutes).

WARNING

Live parts can be easily touched by accident.

Never leave the unit unattended during installation or
servicing when the service panel is removed.

NOTE

Note that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.

Содержание ERSQ011AAV1

Страница 1: ...STALLATION MANUAL ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1 ERRQ011AAV1 ERRQ014AAV1 ERRQ016AAV1 ERSQ011AAY1 ERSQ014AAY1 ERSQ016AAY1 ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1 Outdoor unit for air to water heat pum...

Страница 2: ...L2 H H L2 0 L2 1 2 H 1 2 H L2 H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000...

Страница 3: ...scrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustan...

Страница 4: ...is the original instruction Other languages are translations of the original instructions 1 INTRODUCTION 1 1 General information Thank you for purchasing this unit The outdoor unit is the air to water...

Страница 5: ...check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove...

Страница 6: ...cation e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible 2 When installing the unit in a place exposed to strong wind pay special attention to the following...

Страница 7: ...of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row CAUTION When operating the...

Страница 8: ...In case drain work on your unit is allowed and the installation site requires drain work then follow the guidelines below Drain kits for drainage are available as option If drain work from the outdoo...

Страница 9: ...See the table below concerning lengths and heights Refer to figure 1 Assume that the longest line in the figure corresponds with the actual longest pipe and the highest unit in the figure corresponds...

Страница 10: ...tem and prevents proper operation The nitrogen pressure should be set to 0 02 MPa i e just enough so it can be felt on the skin with a pressure reducing valve Do not use anti oxidants when brazing the...

Страница 11: ...liquid side 4 mm gas side 6 mm into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning The valve is now open Closing the stop valve...

Страница 12: ...the vacuum pump to both the service port of the gas stop valve and the liquid stop valve to increase efficiency Setup See figure 6 Leak test The leak test must satisfy specification EN 378 2 1 Vacuum...

Страница 13: ...cessary amount 8 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigera...

Страница 14: ...arge the additional refrigerant in its liquid state through the service port on the liquid stop valve taking into account following instructions Turn on the power supply of the outdoor unit and indoor...

Страница 15: ...urrent which will have to be discharged with the grounding For Y1 models only Make sure to connect power supply cables in normal phase If connected in reverse phase the remote controller of the indoor...

Страница 16: ...e transmission wires go through the cable outlet port pipe outlet port or knock out hole on either the front side or back of the outdoor unit See figure 8 Precautions when knocking out knockout holes...

Страница 17: ...lues see electrical data of combination with indoor units for exact values 27 A 27 5 A 13 5 A 14 A Transmission line section 0 75 1 25 mm2 Wire type b b Only in protected pipes use H07RN F when protec...

Страница 18: ...maximum allowable pressure as indicated on the nameplate of the unit Provide a logbook In accordance with the relevant national and international regulations it may be neccesary to provide a logbook...

Страница 19: ...et this function ON or OFF push the button as shown below 4 Push the button and the setting is defined 5 When the button is pushed again the operation starts according to the setting Vacuuming method...

Страница 20: ...nal legislation 14 UNIT SPECIFICATIONS Technical specifications Electrical specifications The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by...

Страница 21: ...V1 Y1 3 9 10 1 2 1 2 3 V1 type 1N 50 Hz 220 240 V Y1 type 3N 50 Hz 380 415 V L1 L3 L2 L1 L3 L2 NOTES 10 3 8 2 1 7 6 9 4 4 6 1 4 3 10 4 7 2 9 8 2 10 X2M X3M X1M X2M X1M Y1 V1 3 X2M X3M X2M A2P A1P A1P...

Страница 22: ...4PW49635 1A Copyright Daikin...

Отзывы: