background image

ERSQ+ERRQ011~Y1

Outdoor unit for air to water heat pump

4PW49635-1A 

Installation manual

10

Vacuum drying

To remove all moisture from the system, proceed as follows:

1.

Evacuate the system for at least 2 hours to a target vacuum of 
–100.7 kPa. 

2.

Check that, with the vacuum pump turned off, the target vacuum
is maintained for at least 1 hour. 

3.

Should you fail to reach the target vacuum within 2 hours or
maintain the vacuum for 1 hour, the system may contain too
much moisture. 

4.

In that case, break the vacuum by pressurizing with nitrogen gas
to a gauge pressure of 0.05 MPa (0.5 bar) and repeat steps 1 to
3 until all moisture has been removed. 

5.

The stop valves can now be opened, and/or additional
refrigerant can be charged (see 

"8.3. 

Method for adding

refrigerant" on page 11

).

7.4.

Precautions when connecting field piping and 
regarding insulation

Be careful not to let the indoor and outdoor field piping come into
contact with the compressor terminal cover.
If the liquid-side piping insulation might come into contact with it,
adjust the height as shown in the figure below. Also, make sure
the field piping does not touch the bolts or outer panels of the
compressor.

When the outdoor unit is installed above the indoor unit the
following can occur:
The condensated water on the stop valve can move to the
indoor unit. To avoid this, please cover the stop valve with
sealing material.

If the temperature is higher than 30°C and the humidity is higher
than RH 80%, then the thickness of the sealing materials should
be at least 20 mm in order to avoid condensation on the surface
of the sealing.

Be sure to insulate the liquid and gas-side field piping.

(The highest temperature that the gas-side piping can reach is
around 120°C, so be sure to use insulating material which is
heat resistant.)

8.

C

HARGING

 

REFRIGERANT

To avoid compressor breakdown. Do not charge the refrigerant
more than the specified amount.

This outdoor unit is factory charged with refrigerant and
depending on pipe sizes and pipe lengths some systems require
additional charging of refrigerant. See 

"Calculating the additional

refrigerant charge" on page 11

.

In case re-charge is required, refer to the nameplate of the unit.
The nameplate states the type of refrigerant and necessary
amount.

8.1.

Important information regarding the refrigerant 
used

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Please fill in with indelible ink,

 the factory refrigerant charge of the product,

 the additional refrigerant amount charged in the field and

+

➁ 

the total refrigerant charge

on the fluorinated greenhouse gases label supplied with the product.

The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the
service cover).

After opening the stop valve, it is possible that the pressure
in the refrigerant piping does not rise. This might be
caused by e.g. the closed state of the expansion valve in
the outdoor unit circuit, but does not present any problem
for correct operation of the unit.

Any exposed piping may cause condensation or burns
if touched.

2

1

3

5

5

A

4

4

6

1

Compressor

2

Terminal cover

3

Indoor and outdoor 
field piping

4

Corking, etc.

5

Insulation material 
(field supply)

6

Bolts

A

Be careful with pipe, 
bolt and outer panel 
connections

When servicing the unit requires the refrigerant
system to be opened, treatment and evacuation of
refrigerant must be done in accordance with relevant
local and national legislation.

Refrigerant cannot be charged until field wiring has
been completed.

Refrigerant may only be charged after performing the
leak test and the vacuum drying (see above).

When charging a system, care shall be taken that its
maximum permissible charge is never exceeded, in
view of the danger of liquid hammer.

Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant (R410A) is charged.

Refrigerant containers shall be opened slowly.

Always use protective gloves and protect your eyes
when charging refrigerant.

When performing service on the unit requiring the
refrigerant system to be opened, refrigerant must be
evacuated according to local regulations.

When the power is on, please close the front
panel when leaving the unit.

3

5

6

2

1

4

1

factory refrigerant charge 
of the product:
see unit name plate

2

additional refrigerant 
amount charged in the 
field

3

total refrigerant charge

4

Contains fluorinated 
greenhouse gases 
covered by the Kyoto 
Protocol

5

outdoor unit

6

refrigerant cylinder and 
manifold for charging

Содержание ERSQ011AAV1

Страница 1: ...STALLATION MANUAL ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1 ERRQ011AAV1 ERRQ014AAV1 ERRQ016AAV1 ERSQ011AAY1 ERSQ014AAY1 ERSQ016AAY1 ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1 Outdoor unit for air to water heat pum...

Страница 2: ...L2 H H L2 0 L2 1 2 H 1 2 H L2 H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000...

Страница 3: ...scrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustan...

Страница 4: ...is the original instruction Other languages are translations of the original instructions 1 INTRODUCTION 1 1 General information Thank you for purchasing this unit The outdoor unit is the air to water...

Страница 5: ...check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove...

Страница 6: ...cation e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible 2 When installing the unit in a place exposed to strong wind pay special attention to the following...

Страница 7: ...of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row CAUTION When operating the...

Страница 8: ...In case drain work on your unit is allowed and the installation site requires drain work then follow the guidelines below Drain kits for drainage are available as option If drain work from the outdoo...

Страница 9: ...See the table below concerning lengths and heights Refer to figure 1 Assume that the longest line in the figure corresponds with the actual longest pipe and the highest unit in the figure corresponds...

Страница 10: ...tem and prevents proper operation The nitrogen pressure should be set to 0 02 MPa i e just enough so it can be felt on the skin with a pressure reducing valve Do not use anti oxidants when brazing the...

Страница 11: ...liquid side 4 mm gas side 6 mm into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning The valve is now open Closing the stop valve...

Страница 12: ...the vacuum pump to both the service port of the gas stop valve and the liquid stop valve to increase efficiency Setup See figure 6 Leak test The leak test must satisfy specification EN 378 2 1 Vacuum...

Страница 13: ...cessary amount 8 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigera...

Страница 14: ...arge the additional refrigerant in its liquid state through the service port on the liquid stop valve taking into account following instructions Turn on the power supply of the outdoor unit and indoor...

Страница 15: ...urrent which will have to be discharged with the grounding For Y1 models only Make sure to connect power supply cables in normal phase If connected in reverse phase the remote controller of the indoor...

Страница 16: ...e transmission wires go through the cable outlet port pipe outlet port or knock out hole on either the front side or back of the outdoor unit See figure 8 Precautions when knocking out knockout holes...

Страница 17: ...lues see electrical data of combination with indoor units for exact values 27 A 27 5 A 13 5 A 14 A Transmission line section 0 75 1 25 mm2 Wire type b b Only in protected pipes use H07RN F when protec...

Страница 18: ...maximum allowable pressure as indicated on the nameplate of the unit Provide a logbook In accordance with the relevant national and international regulations it may be neccesary to provide a logbook...

Страница 19: ...et this function ON or OFF push the button as shown below 4 Push the button and the setting is defined 5 When the button is pushed again the operation starts according to the setting Vacuuming method...

Страница 20: ...nal legislation 14 UNIT SPECIFICATIONS Technical specifications Electrical specifications The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by...

Страница 21: ...V1 Y1 3 9 10 1 2 1 2 3 V1 type 1N 50 Hz 220 240 V Y1 type 3N 50 Hz 380 415 V L1 L3 L2 L1 L3 L2 NOTES 10 3 8 2 1 7 6 9 4 4 6 1 4 3 10 4 7 2 9 8 2 10 X2M X3M X1M X2M X1M Y1 V1 3 X2M X3M X2M A2P A1P A1P...

Страница 22: ...4PW49635 1A Copyright Daikin...

Отзывы: