ERSQ+ERRQ011~Y1

Outdoor unit for air to water heat pump

4PW49635-1A 

Installation manual

14

9.5.

Specifications of standard wiring components

A power circuit (see table below) must be provided for connection of
the unit. This circuit must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage breaker.

In connecting the power cable to the power terminal block,
securely clamp the cable as shown in 

figure 8

.

For V1 models only

: Equipment complying with EN/IEC 61000-3-12

(1)

.

Field line connection: Control wiring

The wiring from the indoor unit must be connected to the F1/F2
(In-Out) terminals on the PC board in the outdoor unit.

After installing the interconnecting wires inside the unit, wrap
them along with the on-site refrigerant pipes using finishing
tape, as shown in the figure.

For the above wiring, always use vinyl cords with 0.75 to 1.25 mm

2

sheath or cables (2-core wires). 

Use a power wire pipe for the power wiring.

Outside the unit, make sure the low voltage electric
wiring (i.e. for the remote control, between units, etc.)
and the high voltage electric wiring do not pass near
each other, keeping them at least 50 mm apart.
Proximity may cause electrical interference,
malfunctions, and breakage.

Be sure to connect the power wiring to the power
wiring terminal block and secure it as described under

"9.4. Precautions on wiring of power supply and
inter-unit wiring" on page 13

.

Inter-unit wiring should be secured as described in

"9.4. Precautions on wiring of power supply and
inter-unit wiring" on page 13

.

Secure the wiring with clamps so that it does not touch
the piping.

Make sure the wiring and the electric box lid do not
stick up above the structure, and close the cover
firmly.

ERSQ_V1

ERRQ_V1

ERSQ_Y1

ERRQ_Y1

Phase and frequency

1N~50 Hz

3N~50 Hz

Voltage

220-240 V

380-415 V

Recommended field fuse

32 A

16 A

Minimum circuit amps 

(a)

(a) Stated values are maximum values (see electrical data of combination with 

indoor units for exact values).

27 A

27.5 A

13.5 A

14 A

Transmission line section

0.75~1.25 mm

2

Wire type

(b)

(b) Only in protected pipes, use H07RN-F when protected pipes are not used.

H05VV

NOTE

Select the power supply cable in accordance with
relevant local and national regulations.

Wire size must comply with the applicable local
and national code.

Specifications for local wiring power cord and
branch wiring are in compliance with IEC60245.

The earth leakage circuit breaker must be a
high-speed type breaker of 300 mA (<0.1 s).

After finishing the electric work, confirm that each electric
part and terminal inside the electric parts box is connected
securely.

(1) European/International Technical Standard setting the limits for harmonic 

currents produced by equipment connected to public low-voltage systems 
with input current >16 A and 

75 A per phase.

Precautions when laying power wiring

Use round pressure terminals for connections to the power
terminal block.

When none are available, follow the instructions below.

Do not connect wiring of different thicknesses to the
power terminal block. (Slack in the power wiring may
cause abnormal heat.)

When connecting wiring which is the same thickness,
do as shown in the figure below.

For wiring, use the designated power wire and
connect firmly, then secure to prevent outside
pressure being exerted on the terminal board.

Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.

Over-tightening the terminal screws may break them.

See the table below for tightening torque for the
terminal screws.

Be sure to follow the limits below. If the unit-to-unit cables
are beyond these limits, it may result in malfunction of
transmission.

Maximum wiring length: 300 m
Total wiring length: 600 m

1

2

1

Round pressure 
terminal

2

Power wire

Tightening torque (N•m)

M5 (Power terminal block/ground wire)

2.39~2.92

M4 (Shielded ground)

1.18~1.44

M3.5 (Control wiring block)

0.79~0.97

1

2

3

4

5

4

1

Liquid pipe

2

Gas pipe

3

Interconnecting wiring

4

Insulator

5

Finishing tape

Содержание ERSQ011AAV1

Страница 1: ...STALLATION MANUAL ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1 ERRQ011AAV1 ERRQ014AAV1 ERRQ016AAV1 ERSQ011AAY1 ERSQ014AAY1 ERSQ016AAY1 ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1 Outdoor unit for air to water heat pum...

Страница 2: ...L2 H H L2 0 L2 1 2 H 1 2 H L2 H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000...

Страница 3: ...scrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustan...

Страница 4: ...is the original instruction Other languages are translations of the original instructions 1 INTRODUCTION 1 1 General information Thank you for purchasing this unit The outdoor unit is the air to water...

Страница 5: ...check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove...

Страница 6: ...cation e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible 2 When installing the unit in a place exposed to strong wind pay special attention to the following...

Страница 7: ...of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row CAUTION When operating the...

Страница 8: ...In case drain work on your unit is allowed and the installation site requires drain work then follow the guidelines below Drain kits for drainage are available as option If drain work from the outdoo...

Страница 9: ...See the table below concerning lengths and heights Refer to figure 1 Assume that the longest line in the figure corresponds with the actual longest pipe and the highest unit in the figure corresponds...

Страница 10: ...tem and prevents proper operation The nitrogen pressure should be set to 0 02 MPa i e just enough so it can be felt on the skin with a pressure reducing valve Do not use anti oxidants when brazing the...

Страница 11: ...liquid side 4 mm gas side 6 mm into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning The valve is now open Closing the stop valve...

Страница 12: ...the vacuum pump to both the service port of the gas stop valve and the liquid stop valve to increase efficiency Setup See figure 6 Leak test The leak test must satisfy specification EN 378 2 1 Vacuum...

Страница 13: ...cessary amount 8 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigera...

Страница 14: ...arge the additional refrigerant in its liquid state through the service port on the liquid stop valve taking into account following instructions Turn on the power supply of the outdoor unit and indoor...

Страница 15: ...urrent which will have to be discharged with the grounding For Y1 models only Make sure to connect power supply cables in normal phase If connected in reverse phase the remote controller of the indoor...

Страница 16: ...e transmission wires go through the cable outlet port pipe outlet port or knock out hole on either the front side or back of the outdoor unit See figure 8 Precautions when knocking out knockout holes...

Страница 17: ...lues see electrical data of combination with indoor units for exact values 27 A 27 5 A 13 5 A 14 A Transmission line section 0 75 1 25 mm2 Wire type b b Only in protected pipes use H07RN F when protec...

Страница 18: ...maximum allowable pressure as indicated on the nameplate of the unit Provide a logbook In accordance with the relevant national and international regulations it may be neccesary to provide a logbook...

Страница 19: ...et this function ON or OFF push the button as shown below 4 Push the button and the setting is defined 5 When the button is pushed again the operation starts according to the setting Vacuuming method...

Страница 20: ...nal legislation 14 UNIT SPECIFICATIONS Technical specifications Electrical specifications The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by...

Страница 21: ...V1 Y1 3 9 10 1 2 1 2 3 V1 type 1N 50 Hz 220 240 V Y1 type 3N 50 Hz 380 415 V L1 L3 L2 L1 L3 L2 NOTES 10 3 8 2 1 7 6 9 4 4 6 1 4 3 10 4 7 2 9 8 2 10 X2M X3M X1M X2M X1M Y1 V1 3 X2M X3M X2M A2P A1P A1P...

Страница 22: ...4PW49635 1A Copyright Daikin...

Отзывы: