Installation manual

17

ERSQ+ERRQ011~Y1

Outdoor unit for air to water heat pump

4PW49635-1A

Pump down operation

This unit is equipped with an automatic pump down operation which
will collect all refrigerant from the field piping and indoor unit in the
outdoor unit. To protect the environment, make sure to perform the
following pump down operation when relocating or disposing of the
unit.

1.

Turn on the main power supply.

2.

Make sure the liquid stop valve is closed and the gas stop valve
is open (see 

"6.3. Guidelines for handling stop valve" on

page 8

).

3.

Switch the service mode 2-61 from OFF to ON.

4.

The compressor and outdoor unit fan will start operating
automatically. 
During operation, the LEDs are showing the progress as shown
in the figure.

5.

If step 5 is reached (pressure drops below 3 bar) or if operation
stops (after 30 minutes), close the gas stop valve.

6.

Turn off the main power supply. 

13. D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.

14. U

NIT

 

SPECIFICATIONS

Technical specifications

Electrical specifications

The outdoor unit is equipped with a low pressure
switch or a low pressure sensor to protect the
compressor by switching it off. Never short-circuit the
low pressure switch during pump down operation!

Do not execute the pump down operation if the piping
length between the outdoor unit and the indoor unit is
longer than 10 m. This may cause damage to the unit.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Step 1

x c w w w w w

Step 2

x c x w w w w

Step 3

x c x

x w w w

Step 4

x c x

x

x w w

Step 5

x c x

x

x

x w

Make sure to re-open both stop valves before restarting
operation of the unit.

Model

011

014

016

Casing material

Painted galvanised steel

Dimensions h x w x d

(mm)

1345 x 900 x 320

1345 x 900 x 320

1345 x 900 x 320

Weight

(kg)

120

120

120

Operation range

• heating (min./max)

(°C)

–20/20

–20/20

–20/20

• domestic hot water

(min./max)

(°C)

–20/35

–20/35

–20/35

Refrigerant oil

Daphne FVC68D

Daphne FVC68D

Daphne FVC68D

Piping connection

• liquid

(mm)

9.52

9.52

9.52

• gas

(mm)

15.9

15.9

15.9

Model

011

014

016

V1

Y1

V1

Y1

V1

Y1

Phase

1N~

3N~

1N~

3N~

1N~

3N~

Frequency

(Hz)

50

50

50

Voltage range

• minimum

(V)

220/380

220/380

220/380

• maximum

(V)

240/415

240/415

240/415

Nominal running current

(A)

15.9

5.3

20.2

6.77

22.2

7.79

Содержание ERSQ011AAV1

Страница 1: ...STALLATION MANUAL ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1 ERRQ011AAV1 ERRQ014AAV1 ERRQ016AAV1 ERSQ011AAY1 ERSQ014AAY1 ERSQ016AAY1 ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1 Outdoor unit for air to water heat pum...

Страница 2: ...L2 H H L2 0 L2 1 2 H 1 2 H L2 H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000...

Страница 3: ...scrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustan...

Страница 4: ...is the original instruction Other languages are translations of the original instructions 1 INTRODUCTION 1 1 General information Thank you for purchasing this unit The outdoor unit is the air to water...

Страница 5: ...check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove...

Страница 6: ...cation e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible 2 When installing the unit in a place exposed to strong wind pay special attention to the following...

Страница 7: ...of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row CAUTION When operating the...

Страница 8: ...In case drain work on your unit is allowed and the installation site requires drain work then follow the guidelines below Drain kits for drainage are available as option If drain work from the outdoo...

Страница 9: ...See the table below concerning lengths and heights Refer to figure 1 Assume that the longest line in the figure corresponds with the actual longest pipe and the highest unit in the figure corresponds...

Страница 10: ...tem and prevents proper operation The nitrogen pressure should be set to 0 02 MPa i e just enough so it can be felt on the skin with a pressure reducing valve Do not use anti oxidants when brazing the...

Страница 11: ...liquid side 4 mm gas side 6 mm into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning The valve is now open Closing the stop valve...

Страница 12: ...the vacuum pump to both the service port of the gas stop valve and the liquid stop valve to increase efficiency Setup See figure 6 Leak test The leak test must satisfy specification EN 378 2 1 Vacuum...

Страница 13: ...cessary amount 8 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigera...

Страница 14: ...arge the additional refrigerant in its liquid state through the service port on the liquid stop valve taking into account following instructions Turn on the power supply of the outdoor unit and indoor...

Страница 15: ...urrent which will have to be discharged with the grounding For Y1 models only Make sure to connect power supply cables in normal phase If connected in reverse phase the remote controller of the indoor...

Страница 16: ...e transmission wires go through the cable outlet port pipe outlet port or knock out hole on either the front side or back of the outdoor unit See figure 8 Precautions when knocking out knockout holes...

Страница 17: ...lues see electrical data of combination with indoor units for exact values 27 A 27 5 A 13 5 A 14 A Transmission line section 0 75 1 25 mm2 Wire type b b Only in protected pipes use H07RN F when protec...

Страница 18: ...maximum allowable pressure as indicated on the nameplate of the unit Provide a logbook In accordance with the relevant national and international regulations it may be neccesary to provide a logbook...

Страница 19: ...et this function ON or OFF push the button as shown below 4 Push the button and the setting is defined 5 When the button is pushed again the operation starts according to the setting Vacuuming method...

Страница 20: ...nal legislation 14 UNIT SPECIFICATIONS Technical specifications Electrical specifications The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by...

Страница 21: ...V1 Y1 3 9 10 1 2 1 2 3 V1 type 1N 50 Hz 220 240 V Y1 type 3N 50 Hz 380 415 V L1 L3 L2 L1 L3 L2 NOTES 10 3 8 2 1 7 6 9 4 4 6 1 4 3 10 4 7 2 9 8 2 10 X2M X3M X1M X2M X1M Y1 V1 3 X2M X3M X2M A2P A1P A1P...

Страница 22: ...4PW49635 1A Copyright Daikin...

Отзывы: