Installation manual
17
ERSQ+ERRQ011~Y1
Outdoor unit for air to water heat pump
4PW49635-1A
Pump down operation
This unit is equipped with an automatic pump down operation which
will collect all refrigerant from the field piping and indoor unit in the
outdoor unit. To protect the environment, make sure to perform the
following pump down operation when relocating or disposing of the
unit.
1.
Turn on the main power supply.
2.
Make sure the liquid stop valve is closed and the gas stop valve
is open (see
"6.3. Guidelines for handling stop valve" on
page 8
).
3.
Switch the service mode 2-61 from OFF to ON.
4.
The compressor and outdoor unit fan will start operating
automatically.
During operation, the LEDs are showing the progress as shown
in the figure.
5.
If step 5 is reached (pressure drops below 3 bar) or if operation
stops (after 30 minutes), close the gas stop valve.
6.
Turn off the main power supply.
13. D
ISPOSAL
REQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
14. U
NIT
SPECIFICATIONS
Technical specifications
Electrical specifications
■
The outdoor unit is equipped with a low pressure
switch or a low pressure sensor to protect the
compressor by switching it off. Never short-circuit the
low pressure switch during pump down operation!
■
Do not execute the pump down operation if the piping
length between the outdoor unit and the indoor unit is
longer than 10 m. This may cause damage to the unit.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Step 1
x c w w w w w
Step 2
x c x w w w w
Step 3
x c x
x w w w
Step 4
x c x
x
x w w
Step 5
x c x
x
x
x w
Make sure to re-open both stop valves before restarting
operation of the unit.
Model
011
014
016
Casing material
Painted galvanised steel
Dimensions h x w x d
(mm)
1345 x 900 x 320
1345 x 900 x 320
1345 x 900 x 320
Weight
(kg)
120
120
120
Operation range
• heating (min./max)
(°C)
–20/20
–20/20
–20/20
• domestic hot water
(min./max)
(°C)
–20/35
–20/35
–20/35
Refrigerant oil
Daphne FVC68D
Daphne FVC68D
Daphne FVC68D
Piping connection
• liquid
(mm)
9.52
9.52
9.52
• gas
(mm)
15.9
15.9
15.9
Model
011
014
016
V1
Y1
V1
Y1
V1
Y1
Phase
1N~
3N~
1N~
3N~
1N~
3N~
Frequency
(Hz)
50
50
50
Voltage range
• minimum
(V)
220/380
220/380
220/380
• maximum
(V)
240/415
240/415
240/415
Nominal running current
(A)
15.9
5.3
20.2
6.77
22.2
7.79