Installation manual

5

ERSQ+ERRQ011~Y1

Outdoor unit for air to water heat pump

4PW49635-1A

2.

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions between H, A and L is shown in the table
below.

4.4.

Inspecting, handling and unpacking the unit

Handling the unit

As shown in the figure, bring the unit slowly by grabbing the left and
right grips.

Place your hands on the corner instead of holding the suction inlet in
the side of the casing, otherwise the casing could be deformed.

Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown
in the figure.

prepare all 4 wires as indicated in the drawing

unscrew the top plate at the 4 locations indicated A and B

put the screws through the nooses and screw them back tight

A

location of the 2 fixation holes on the front side of the unit

B

location of the 2 fixation holes on the rear side of the unit

C

wires: field supply

Method for removing transportation stay

The yellow transportation stay installed over the compressor leg for
protecting the unit during transport must be removed. Proceed as
shown in 

figure 3

 and described below.

1

Slightly loosen the fixing nut (

B

).

2

Remove the transportation stay (

C

) as shown in 

figure 3

.

3

Tighten the fixing nut (

B

) again.

4.5.

Drain work

Check in the combination table under 

"General information" on

page 1

 whether drain work is allowed. In case drain work on your unit

is allowed and the installation site requires drain work, then follow the
guidelines below.

Drain kits for drainage are available as option.

If drain work from the outdoor unit causes trouble (for example, if
the drain water may splash on people) provide the drain piping
using a drain socket (optional).

Make sure the drain works properly.

4.6.

Installing the unit

Precautions for R410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-

Clean and dry
Foreign materials (including mineral oils or moisture) should 
be prevented from getting mixed into the system.

-

Tight
Read 

"6. Precautions on refrigerant piping" on page 7

 

carefully and follow these procedures correctly.

Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant
is in state of gas, its composition changes and the system will
not work properly).

The connected indoor unit must be the EKHBRD unit.

L

A

L

H

0<L

1/2H

250

1/2H<L

H

300

H<L

Installation impossible

Take care not to let hands or objects come in contact with
rear fins.

1500

600

3000

A

H

L

C

B

A

A

A

Compressor

B

Fixing nut

C

Transportation stay

CAUTION

If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.

NOTE

If drain holes of the outdoor unit
are covered by a mounting base
or by floor surface, raise the unit
in order to provide a free space
of more than 100 mm under the
outdoor unit.

Since design pressure is 4.0 MPa or 40 bar, pipes of larger
wall thickness may be required. Refer to paragraph

"5.1. Selection of piping material" on page 6

.

Содержание ERSQ011AAV1

Страница 1: ...STALLATION MANUAL ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1 ERRQ011AAV1 ERRQ014AAV1 ERRQ016AAV1 ERSQ011AAY1 ERSQ014AAY1 ERSQ016AAY1 ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1 Outdoor unit for air to water heat pum...

Страница 2: ...L2 H H L2 0 L2 1 2 H 1 2 H L2 H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000...

Страница 3: ...scrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustan...

Страница 4: ...is the original instruction Other languages are translations of the original instructions 1 INTRODUCTION 1 1 General information Thank you for purchasing this unit The outdoor unit is the air to water...

Страница 5: ...check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove...

Страница 6: ...cation e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible 2 When installing the unit in a place exposed to strong wind pay special attention to the following...

Страница 7: ...of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row CAUTION When operating the...

Страница 8: ...In case drain work on your unit is allowed and the installation site requires drain work then follow the guidelines below Drain kits for drainage are available as option If drain work from the outdoo...

Страница 9: ...See the table below concerning lengths and heights Refer to figure 1 Assume that the longest line in the figure corresponds with the actual longest pipe and the highest unit in the figure corresponds...

Страница 10: ...tem and prevents proper operation The nitrogen pressure should be set to 0 02 MPa i e just enough so it can be felt on the skin with a pressure reducing valve Do not use anti oxidants when brazing the...

Страница 11: ...liquid side 4 mm gas side 6 mm into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning The valve is now open Closing the stop valve...

Страница 12: ...the vacuum pump to both the service port of the gas stop valve and the liquid stop valve to increase efficiency Setup See figure 6 Leak test The leak test must satisfy specification EN 378 2 1 Vacuum...

Страница 13: ...cessary amount 8 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigera...

Страница 14: ...arge the additional refrigerant in its liquid state through the service port on the liquid stop valve taking into account following instructions Turn on the power supply of the outdoor unit and indoor...

Страница 15: ...urrent which will have to be discharged with the grounding For Y1 models only Make sure to connect power supply cables in normal phase If connected in reverse phase the remote controller of the indoor...

Страница 16: ...e transmission wires go through the cable outlet port pipe outlet port or knock out hole on either the front side or back of the outdoor unit See figure 8 Precautions when knocking out knockout holes...

Страница 17: ...lues see electrical data of combination with indoor units for exact values 27 A 27 5 A 13 5 A 14 A Transmission line section 0 75 1 25 mm2 Wire type b b Only in protected pipes use H07RN F when protec...

Страница 18: ...maximum allowable pressure as indicated on the nameplate of the unit Provide a logbook In accordance with the relevant national and international regulations it may be neccesary to provide a logbook...

Страница 19: ...et this function ON or OFF push the button as shown below 4 Push the button and the setting is defined 5 When the button is pushed again the operation starts according to the setting Vacuuming method...

Страница 20: ...nal legislation 14 UNIT SPECIFICATIONS Technical specifications Electrical specifications The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by...

Страница 21: ...V1 Y1 3 9 10 1 2 1 2 3 V1 type 1N 50 Hz 220 240 V Y1 type 3N 50 Hz 380 415 V L1 L3 L2 L1 L3 L2 NOTES 10 3 8 2 1 7 6 9 4 4 6 1 4 3 10 4 7 2 9 8 2 10 X2M X3M X1M X2M X1M Y1 V1 3 X2M X3M X2M A2P A1P A1P...

Страница 22: ...4PW49635 1A Copyright Daikin...

Отзывы: