ERSQ+ERRQ011~Y1

Outdoor unit for air to water heat pump

4PW49635-1A 

Installation manual

4

Selecting a location in cold climates

Refer to 

"General information" on page 1

.

To  prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.

Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.

To  prevent exposure to wind, install a baffle plate on the air
discharge side of the outdoor unit.

In heavy snowfall areas it is very important to select an
installation site where the snow will not affect the unit. If lateral
snowfall is possible, make sure that the heat exchanger coil is
not affected by the snow (if necessary construct a lateral
canopy).

4.2.

Precautions on installation

Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.

In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four
sets of M12 foundation bolts, nuts and washers each which are
available on the market.)

It is best to screw in the foundation bolts until their length are
20 mm from the foundation surface.

4.3.

Dimensions and servicing space

The connection piping outlet direction in the installation shown in

figure 4

  is frontward or downward. The unit of numeric values

is mm.

When routing the piping backward, secure space of 

250 mm on

the right side of the unit.

(A) In case of non-stacked installation 

(See figure 4)

(B) In case of stacked installation

1.

In case obstacles exist in front of the outlet side.

2.

In case obstacles exist in front of the air inlet.

(C) In case of multiple-row installation (for roof top use, etc.)

1.

In case of installing one unit per row.

CAUTION

When operating the outdoor unit in a low outdoor ambient
temperature, be sure to follow the instructions described
below.

The equipment described in this manual may cause
electronic noise generated from radio-frequency energy.
The equipment complies to specifications that are
designed to provide reasonable protection against such
interference. However, there is no guarantee that
interference will not occur in a particular installation.

It is therefore recommended to install the equipment and
electric wires keeping proper distances away from stereo
equipment, personal computers, etc... 

(See figure 2)

1

Personal computer or radio

2

Indoor unit

3

Outdoor unit

In extreme circumstances you should keep distances of

m or more and use conduit tubes for power and

transmission lines.

Discharge side

Bottom view (mm)

Drain hole

1

2

1

Construct a large canopy.

2

Construct a pedestal.
Install the unit high enough off 
the ground to prevent burying in 
snow.

20

140

117

219

289

350

(345-355)

47

140

620

614

423

A

B

C

Suction side obstacle

1

In these cases, close the 
bottom of the installation 
frame to prevent the 
discharged air from 
being bypassed

Discharge side obstacle

Left side obstacle

2

In these cases, only 2 
units can be installed.

Right side obstacle

3

In these cases, no 
restriction of height L1.

Top side obstacle

This situation is not 
allowed

Obstacle is present

NOTE

Do not stack more than one unit.

About 100 mm is required as the dimension
for laying the upper outdoor unit's drain pipe.

Get the portion A sealed so that air from the
outlet does not bypass.

1000

100

A

300

100

A

1000

200

2000

100

Содержание ERSQ011AAV1

Страница 1: ...STALLATION MANUAL ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1 ERRQ011AAV1 ERRQ014AAV1 ERRQ016AAV1 ERSQ011AAY1 ERSQ014AAY1 ERSQ016AAY1 ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1 Outdoor unit for air to water heat pum...

Страница 2: ...L2 H H L2 0 L2 1 2 H 1 2 H L2 H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000...

Страница 3: ...scrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustan...

Страница 4: ...is the original instruction Other languages are translations of the original instructions 1 INTRODUCTION 1 1 General information Thank you for purchasing this unit The outdoor unit is the air to water...

Страница 5: ...check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove...

Страница 6: ...cation e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible 2 When installing the unit in a place exposed to strong wind pay special attention to the following...

Страница 7: ...of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row CAUTION When operating the...

Страница 8: ...In case drain work on your unit is allowed and the installation site requires drain work then follow the guidelines below Drain kits for drainage are available as option If drain work from the outdoo...

Страница 9: ...See the table below concerning lengths and heights Refer to figure 1 Assume that the longest line in the figure corresponds with the actual longest pipe and the highest unit in the figure corresponds...

Страница 10: ...tem and prevents proper operation The nitrogen pressure should be set to 0 02 MPa i e just enough so it can be felt on the skin with a pressure reducing valve Do not use anti oxidants when brazing the...

Страница 11: ...liquid side 4 mm gas side 6 mm into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning The valve is now open Closing the stop valve...

Страница 12: ...the vacuum pump to both the service port of the gas stop valve and the liquid stop valve to increase efficiency Setup See figure 6 Leak test The leak test must satisfy specification EN 378 2 1 Vacuum...

Страница 13: ...cessary amount 8 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigera...

Страница 14: ...arge the additional refrigerant in its liquid state through the service port on the liquid stop valve taking into account following instructions Turn on the power supply of the outdoor unit and indoor...

Страница 15: ...urrent which will have to be discharged with the grounding For Y1 models only Make sure to connect power supply cables in normal phase If connected in reverse phase the remote controller of the indoor...

Страница 16: ...e transmission wires go through the cable outlet port pipe outlet port or knock out hole on either the front side or back of the outdoor unit See figure 8 Precautions when knocking out knockout holes...

Страница 17: ...lues see electrical data of combination with indoor units for exact values 27 A 27 5 A 13 5 A 14 A Transmission line section 0 75 1 25 mm2 Wire type b b Only in protected pipes use H07RN F when protec...

Страница 18: ...maximum allowable pressure as indicated on the nameplate of the unit Provide a logbook In accordance with the relevant national and international regulations it may be neccesary to provide a logbook...

Страница 19: ...et this function ON or OFF push the button as shown below 4 Push the button and the setting is defined 5 When the button is pushed again the operation starts according to the setting Vacuuming method...

Страница 20: ...nal legislation 14 UNIT SPECIFICATIONS Technical specifications Electrical specifications The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by...

Страница 21: ...V1 Y1 3 9 10 1 2 1 2 3 V1 type 1N 50 Hz 220 240 V Y1 type 3N 50 Hz 380 415 V L1 L3 L2 L1 L3 L2 NOTES 10 3 8 2 1 7 6 9 4 4 6 1 4 3 10 4 7 2 9 8 2 10 X2M X3M X1M X2M X1M Y1 V1 3 X2M X3M X2M A2P A1P A1P...

Страница 22: ...4PW49635 1A Copyright Daikin...

Отзывы: