ERSQ+ERRQ011~Y1

Outdoor unit for air to water heat pump

4PW49635-1A 

Installation manual

8

Not recommended, but in case of emergency
Should you be forced to connect the piping without a torque
wrench, follow the following installation method:

Tighten the flare nut using a spanner until the tightening
torque suddenly increases.

From that position further tighten the flare nut the angle listed
below:

6.3.

Guidelines for handling stop valve

Cautions on handling the stop valve

Make sure to keep both stop valves open during operation.

The figure below shows the name of each part required in
handling the stop valve.

The stop valve is factory closed.

Do not apply excessive force to the stop valve. Doing so may
break the valve body.
Since the stop valve mounting plate may be deformed if only a
torque wrench is used to loosen or tighten the flare nut, always
make sure to secure the stop valve with a spanner, then loosen
or tighten the flare nut with a torque wrench.
Do not place the spanner on the stop valve cover, as this could
cause a refrigerant leak.

The operating pressure at the refrigerant side can be low (for
example, heating operation when outdoor temperature is low),
sufficiently seal the flare nut in the stop valve on the gas line with
silicon sealant to prevent freezing.

Opening/closing the stop valve

Opening the stop valve

1.

Remove the valve cover.

2.

Insert a hexagon wrench (liquid side: 4 mm/gas side: 6 mm) into
the stop valve and turn the stop valve counterclockwise.

3.

When the stop valve cannot be turned any further, stop turning. 
The valve is now open.

Closing the stop valve

1.

Remove the valve cover.

2.

Insert a hexagon wrench (liquid side: 4 mm/gas side: 6 mm) into
the stop valve and turn the stop valve clockwise.

3.

When the stop valve cannot be turned any further, stop turning. 
The valve is now closed.

Cautions on handling the stop valve cover

The stop valve cover is sealed
where indicated by the arrow. Take
care not to damage it.

After handling the stop valve, make
sure to tighten the stop valve cover
securely. For the tightening torque,
refer to the table below.

Check for refrigerant leaks after tightening the stop valve cover.

Cautions on handling the service port

Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.

After handling the service port, make sure to tighten the service
port cover securely. For the tightening torque, refer to the table
below.

Check for refrigerant leaks after tightening the service port
cover.

Tightening torques

Piping size

(mm)

Further tightening 

angle (degrees)

Recommended arm 

length of spanner (mm)

Ø9.5

60~90

±200

Ø15.9

30~60

±300

 Silicon sealing pad
 (Make sure there is no gap)

3

4

1

2

1

Service port and service port cover

2

Stop valve

3

Field piping connection

4

Stop valve cover

1

2

1

Spanner

2

Torque wrench

Closing direction

Liquid side

Gas side

Item

Tightening torque (N•m)

Stop valve cover, liquid side

13.5~16.5

Stop valve cover, gas side

22.5~27.5

Service port cover

11.5~13.9

Содержание ERSQ011AAV1

Страница 1: ...STALLATION MANUAL ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1 ERRQ011AAV1 ERRQ014AAV1 ERRQ016AAV1 ERSQ011AAY1 ERSQ014AAY1 ERSQ016AAY1 ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1 Outdoor unit for air to water heat pum...

Страница 2: ...L2 H H L2 0 L2 1 2 H 1 2 H L2 H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000...

Страница 3: ...scrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustan...

Страница 4: ...is the original instruction Other languages are translations of the original instructions 1 INTRODUCTION 1 1 General information Thank you for purchasing this unit The outdoor unit is the air to water...

Страница 5: ...check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove...

Страница 6: ...cation e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible 2 When installing the unit in a place exposed to strong wind pay special attention to the following...

Страница 7: ...of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row CAUTION When operating the...

Страница 8: ...In case drain work on your unit is allowed and the installation site requires drain work then follow the guidelines below Drain kits for drainage are available as option If drain work from the outdoo...

Страница 9: ...See the table below concerning lengths and heights Refer to figure 1 Assume that the longest line in the figure corresponds with the actual longest pipe and the highest unit in the figure corresponds...

Страница 10: ...tem and prevents proper operation The nitrogen pressure should be set to 0 02 MPa i e just enough so it can be felt on the skin with a pressure reducing valve Do not use anti oxidants when brazing the...

Страница 11: ...liquid side 4 mm gas side 6 mm into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning The valve is now open Closing the stop valve...

Страница 12: ...the vacuum pump to both the service port of the gas stop valve and the liquid stop valve to increase efficiency Setup See figure 6 Leak test The leak test must satisfy specification EN 378 2 1 Vacuum...

Страница 13: ...cessary amount 8 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigera...

Страница 14: ...arge the additional refrigerant in its liquid state through the service port on the liquid stop valve taking into account following instructions Turn on the power supply of the outdoor unit and indoor...

Страница 15: ...urrent which will have to be discharged with the grounding For Y1 models only Make sure to connect power supply cables in normal phase If connected in reverse phase the remote controller of the indoor...

Страница 16: ...e transmission wires go through the cable outlet port pipe outlet port or knock out hole on either the front side or back of the outdoor unit See figure 8 Precautions when knocking out knockout holes...

Страница 17: ...lues see electrical data of combination with indoor units for exact values 27 A 27 5 A 13 5 A 14 A Transmission line section 0 75 1 25 mm2 Wire type b b Only in protected pipes use H07RN F when protec...

Страница 18: ...maximum allowable pressure as indicated on the nameplate of the unit Provide a logbook In accordance with the relevant national and international regulations it may be neccesary to provide a logbook...

Страница 19: ...et this function ON or OFF push the button as shown below 4 Push the button and the setting is defined 5 When the button is pushed again the operation starts according to the setting Vacuuming method...

Страница 20: ...nal legislation 14 UNIT SPECIFICATIONS Technical specifications Electrical specifications The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by...

Страница 21: ...V1 Y1 3 9 10 1 2 1 2 3 V1 type 1N 50 Hz 220 240 V Y1 type 3N 50 Hz 380 415 V L1 L3 L2 L1 L3 L2 NOTES 10 3 8 2 1 7 6 9 4 4 6 1 4 3 10 4 7 2 9 8 2 10 X2M X3M X1M X2M X1M Y1 V1 3 X2M X3M X2M A2P A1P A1P...

Страница 22: ...4PW49635 1A Copyright Daikin...

Отзывы: