PIM00587
EN-59
CHAPTER 11
PARAMETER ADJUSTMENT
11.1
Parameter List
The default value of the parameter P10, P13 to 28, and P31 is different, depending on the unit type.
Refer to page 63
“
Table 1: Different default parameter values for different products
” for the default value of
the parameter P10 and P31.
Panel
Indication
Code
Name
Operation Range
Default
Value
Details
P00
DI_A
Start/stop
signal
switching
0: Runs at DIN0-ON
1: Runs at DIN0-OFF
1
DIN0: Sets the effective logic for the start/stop
signal.
P01
SW_L
Pressure
switch
0 - 35.0 [MPa]
0
Sets the actuation value of the pressure switch. If
set to “0”, the pressure switch function is
disabled.
P08 : When AMIX = 2, it is in [%] units.
0 to 507 [×10PSI]
0
0 to 350 [%]
0
P02
T_SW
Pressure
switch output
delay time
0.00 to 9.99 [sec]
0.00
Sets the delay time from when the pressure falls
below the set value for “P01: Pressure switch” to
confirmation of the pressure drop.
P03
PSWH
Pressure
switch
indication
retention
setting
0 to 2
0
When the “L63: Pressure switch actuation”
warning has occurred, the “L63” indication
displayed on the operation panel can be retained.
It is also possible to record the “L63:
Pressure
switch actuation” warning in the alarm history,
although it is not usually recorded there.
Value
L63
Indication
Retention
Recording in
Alarm History
0
Not retained
No recorded
1
Retained
No recorded
2
Retained
Recorded
P04
DS_P
Pressure unit
selection
setting*
0: MPa indication
1: PSI indication
0
Enables selection of the display unit for pressures
displayed on the panel.
P05
K_RT
Load
command rate
at the time of
regeneration
30 to 100 [%]
100
Set the deceleration torque during regenerative
operation.
If you decrease the value, the regeneration load
rate will decrease, but the deceleration time will
become longer.
P06
D_RT
Regenerative
load ratio
command at
the time of
deceleration
0 to 100 [%]
0
When you want to change the PQ selection, if the
deceleration is more than 50% of the maximum
flow, set the deceleration torque.
If this value decreases, the regenerative load ratio
will decrease, but the deceleration time will be
longer.
If the default setting is 0, this function will be
disabled. At this time, it’s not necessary to
change the setting.