PIM00587
EN-69
11.4
Function of Run / Stop of the Motor Pump
Turning the power ON/OFF frequently significantly shortens the life of the controller. By using this function, it
will encourage longer life of the controller than power shutdown. A pump can be started / stopped by
inputting a signal from the outside to the digital input terminal DIN1. Refer to the following internal circuit
and connect the wiring.
Panel
Indication
Name
Operation Range
Default
Value
Unit
P00
Start/stop
signal
switching
Set Value
State of DIN1 terminal
OFF
ON
0
STOPS
RUNS
1
RUNS
STOPS
1
CAUTION
Prepare a DC24 V ±10%/0.5 A power supply externally.
It is not possible to supply power from this controller to external destinations.
The current flowing to each input circuit is 5mA(typ.). If a circuit is configured with contacts, etc., pay
attention to the minimum current for those contacts, etc.
Please wait at least 0.5 seconds before starting restart from stop command.
Frequently turning ON / OFF the power supply may damage the controller.
Please turn ON / OFF the
pump by this function except in an emergency.
Internal circuit
DIN1
DIN2
DIN5
ICOM
4.7 kΩ
0.1
u
F
5 mA
1 k
Ω
External power
supply
DC24 V
Please connect the wiring here