PIM00587
EN-60
Panel
Indication
Code
Name
Operation Range
Default
Value
Details
P07
WN_M
Warning output
level setting
0 to 2
0
Set the output signal at the time of warning
occurrence. Refer to " P08: Alarm output mix " for
more information.
P08
AMIX
Alarm output
mix
0 : Individual output
1 : Integrated output
2 : Pressure switch
function expansion
1
Select the output method and output terminal of
the alarm signal, pressure switch signal and
warning signal,
The working pressure of the pressure switch,
which is set in : “P01 : Pressure switch” can be
selected as follows.
*I
f you want to change the settings of “P01 :
Pressure switch”, it will be enabled by turning on
the power again.
R
efer to “
11.6 Function of the Pressure Switch
for more information.
P08
P07
DO2
Contact
output
0 or 2
0
ON : Normal
OFF : Alarm
Pressure
switch
1
ON : Normal
OFF : Alarm
ON
⇔
OFF :
Warning
2
ON : Normal
OFF : Alarm
or Warning
1
0
No output
Alarm or
Pressure
switch
1
Alarm or
Pressure
switch or
warning
P08
Working pressure of
“P01 : Pressure switch”
Unit
0 or 1 Fixed value
[MPa]
2
The ratio of the pressure
setting of each PQ
number
[%]
P09
INIF
Initialize to
defaults
0: Disable
1: Initialize P00 to P09
2: Initialize all parameters
0
Setting “1” or “2” then turning the power off and
back on initializes parameters to their default
values according to the setting made.
P10
L_TI
Response gain 5 to 999
*1
Decreasing the set value makes the response to
pressure / flow rate increase / decrease faster, but
the more surge pressure occurs. Enabled when
“P59: NO_S PQ control method selection” is set
to 0: Control A.
P11
M_VR
Acceleration
response gain
0 to 500
200
Increasing the set value makes the response to
pressure / flow rate increase / decrease faster, but
the more surge pressure occurs.
“0” is an
invalid value, which is equivalent to
setting it to the maximum value.
Enabled when
“P59: NO_S PQ control method
selection” is set to 0: Control A.