PIM00587 

EN-60 

Panel 

Indication 

Code 

Name 

Operation Range 

Default 

Value 

Details 

P07 

WN_M 

Warning output 
level setting 

0 to 2 

Set the output signal at the time of warning 
occurrence. Refer to " P08: Alarm output mix " for 
more information. 

P08 

AMIX 

Alarm output 
mix 

0 : Individual output 
1 : Integrated output 
2 : Pressure switch 

 function expansion 

Select the output method and output terminal of 
the alarm signal, pressure switch signal and 
warning signal, 

The working pressure of the pressure switch, 

which is set in : “P01 : Pressure switch” can be 

selected as follows. 

*I

f you want to change the settings of “P01 : 

Pressure switch”, it will be enabled by turning on 

the power again. 
R

efer to 

11.6 Function of the Pressure Switch

” 

for more information. 

P08 

P07 

DO2 

Contact 

output 

0 or 2 

ON   : Normal 
OFF : Alarm 

Pressure 
switch 

ON   : Normal 
OFF : Alarm 
ON 

 OFF : 

 Warning 

ON   : Normal 
OFF : Alarm 
or Warning 

No output 

Alarm or 
Pressure 
switch 

Alarm or 
Pressure 
switch or 
warning 

P08 

Working pressure of 

“P01 : Pressure switch”

 

Unit 

0 or 1  Fixed value 

[MPa] 

The ratio of the pressure 
setting of each PQ 
number 

[%] 

P09 

INIF 

Initialize to 
defaults 

0: Disable 
1: Initialize P00 to P09 
2: Initialize all parameters 

Setting “1” or “2” then turning the power off and 

back on initializes parameters to their default 
values according to the setting made. 

P10 

L_TI 

Response gain  5 to 999 

*1 

Decreasing the set value makes the response to 
pressure / flow rate increase / decrease faster, but 
the more surge pressure occurs. Enabled when 

“P59: NO_S PQ control method selection” is set 

to 0: Control A. 

P11 

M_VR 

Acceleration 
response gain 

0 to 500 

200 

Increasing the set value makes the response to 
pressure / flow rate increase / decrease faster, but 
the more surge pressure occurs.  

“0” is an 

invalid value, which is equivalent to 

setting it to the maximum value. 
Enabled when 

“P59: NO_S PQ control method 

selection” is set to 0: Control A.

 

Содержание ECORICH R 40 Series

Страница 1: ...b r i d H y d r a u l i c S y s t e m Design 40 Series EHU15R0700 40 03 EHU15R0702 40 EHU15R0703 40 03 EHU15R1000 40 03 EHU15R1002 40 EHU15R1003 40 03 EHU30R0700 40 03 EHU30R0702 40 EHU30R0703 40 03 J...

Страница 2: ...CHAPTER 4 PROCEDURE FOR STARTING UP EN 23 CHAPTER 5 CHECKS UPON RECEIVING THE PRODUCT EN 24 5 1 Check on the Contents of the Packaging EN 24 5 2 Check on the Model EN 24 CHAPTER 6 TRANSPORTATION INSTA...

Страница 3: ...ion of Run Stop of the Motor Pump EN 69 11 5 Function of the Output of the Alarm Status and Warning Status EN 70 11 5 1 Contact output EN 70 11 5 2 Digital output EN 71 11 5 3 Contact output and digit...

Страница 4: ...12 9 2 Cleaning EN 93 12 10 Suction Strainer Maintenance Instructions EN 94 12 10 1 Removal method EN 94 12 10 2 Cleaning EN 95 12 10 3 Reassembly EN 95 12 11 Safety Valve Adjustment Instructions EN...

Страница 5: ...without regard to this indication will cause a potentially hazardous condition that may result in moderate or slight injury or property damage NOTICE Improper handling without regard to this indicatio...

Страница 6: ...N shall not be responsible for any damage attributable to fire earthquake a third party s action or other accidents or customers intentional acts misuse or use under abnormal conditions DAIKIN shall n...

Страница 7: ...es partly completed machinery in the sense of the EC Machinery Directive 2006 42 EC and respectively not usable This product is exclusively intended for integration into a machine or system or for ass...

Страница 8: ...ove Refer to the specification documents External dimension sheet for other specifications This manual is subject to change in order to improve the usability of the user s manual and to change the spe...

Страница 9: ...risk of electric shock and breakage To move this product use the eye bolts Hoisting it by the pump piping for example will pose a danger of the product falling or overturning Do not install or run thi...

Страница 10: ...ine Otherwise there is a risk of injury and failures of the machine Before running the product ensure that you will be able to effect an emergency stop at any time Otherwise there is a risk of injury...

Страница 11: ...is a risk of electric shock accidents and damage Do not disassemble this product Otherwise there is a risk of electric shock and injury CAUTION Wear protective glasses and gloves for this work Do not...

Страница 12: ...e 1 6 5 Warning plates WARNING The warning plates are very important so do not damage or remove them If a warning plate becomes difficult to read through peeling or losses contact Daikin immediately T...

Страница 13: ...5 15 2 3 5 28 5 Coating color Black Purchased parts etc standard color of the equipment manufacturer Digital input 5 channels Photo coupler insulation DC 24 V max 27 V 5 mA positive or negative common...

Страница 14: ...combination of those tabled below or codes 11 to 99 when combined Unit options Tank capacity code Description Tank capacity code Description 00 02 03 00 02 03 Code Code 22 Controller cover 07 54 Leve...

Страница 15: ...secure with bolts etc Other Be sure to install no fuse breakers at all poles 3 poles or 2 poles at the main circuit power supply side primary side Wire electrical connections so as to satisfy JIS B 9...

Страница 16: ...nuous discharge flow rate at the maximum operating pressure according to the model EHU15R 3 L min or less EHU30R 5 L min or less EHU15R0700 40 03 EHU15R0703 40 03 EHU15R1000 40 03 EHU15R1003 40 03 EHU...

Страница 17: ...PIM00587 EN 16 2 4 External Dimensions Motor pump type EHU15 30R 00 03 M8 bolts recommend...

Страница 18: ...PIM00587 EN 17 20L tank unit type EHU15 30R 02 4 13 holes positions 4 10 holes positions Oil filling drain port Section at A A Dimensions of mounting holes for installation...

Страница 19: ...3 Both front and back sides M12 bolts recommended Separately arranged items Cap nut is welded to back side Dimension when attached the installation plate Dimension when attached the installation plate...

Страница 20: ...e EHU15 30R 02 Part No Name 1 1 Inverter driven motor pump 1 2 Control unit 2 DC fan 3 Base Part No Name 1 Oil tank 18L 2 Suction strainer 3 Oil level gauge 4 1 Inverter driven motor pump 4 2 Control...

Страница 21: ...type EHU15 30R 03 03 Part No Name 1 Oil tank 33L 2 Suction strainer 3 Stop valve 4 Oil level gauge 5 Oil filler port cum air breather 6 1 Inverter driven motor pump 6 1 Control unit 7 Oil cooler Abov...

Страница 22: ...t type EHU15 30R 02 Operation panel Control unit DC fan Front View of Unit Valve block Inverter driven motor pump Operation panel Control unit Oil cooler DC fan Oil tank Front View of Unit Valve block...

Страница 23: ...e EHU15 30R 03 03 Operation panel Control unit Oil cooler DC fan Front View of Unit Inverter driven motor pump Oil filler port cum air breather Oil level gauge Stop valve Oil tank Top View of Unit Val...

Страница 24: ...to check the following points before turning the power on Is the product installed correctly Has the piping been done correctly Has hydraulic oil been supplied Has the wiring been done correctly Is t...

Страница 25: ...items are present Hydraulic unit body 1 piece Instruction Manual 1 copy 5 2 Check on the Model Check with the product nameplates that the actual item matches the ordered product The nameplate positio...

Страница 26: ...equipment appropriate for the packaged state Otherwise there is a danger of falling or toppling over This is a heavy item and should therefore not be lifted by one person alone Check the product s wei...

Страница 27: ...ulic unit in the table above and ensure that the hoisting load is within the rated load of the hoisting equipment NOTICE Do not move the product while there is oil in the tank this could cause malfunc...

Страница 28: ...icient maintenance space so that working postures will not be uncomfortable NOTICE If the intake air exhaust spaces described above are not secured the motor and controller will reach high temperature...

Страница 29: ...od and position refer to the Delivery Specification outline drawing Motor pump type EHU15 30R 00 03 20L tank unit type EHU15 30R 02 Installation Mounting Hole Dimensions 490 314 4 10 M8 bolts recommen...

Страница 30: ...a hazard Be sure to secure it with bolts etc NOTICE Installing the product on a sloping surface may cause oil leakage and inclusion of air in the oil leading to abnormal noises and shortening of equi...

Страница 31: ...s not equipped with an oil cooler Use the cooling equipment separately so that they can be used at an appropriate oil temperature Piping Specifications Piping Port Piping Size Recommended Hose Withsta...

Страница 32: ...bottom 10cm or more Ensure the distance between the suction port and the return port Or put a baffle plate partition plate Install a filter 40 m or less to the air breather Design the oil tank and mak...

Страница 33: ...with sealing tape Piping Specifications Piping Port Piping Size Recommended Hose Withstand Pressure At Shipment P Rc 3 8 EHU R07 10 5 MPa EHU R10 14 0 MPa Vinyl cap DR Rp 3 4 1 5 MPa T1 Rc 1 1 5 MPa...

Страница 34: ...he weight of the hose support the hose 7 2 Filling with Hydraulic Oil Tank Unit Type only Remove the cap of the filler port cum air breather by turning it counterclockwise then pour clean hydraulic oi...

Страница 35: ...the tank may decrease Add oil to bring the height of the oil level to within the stipulated range Depending on the volumetric capacity of the hydraulic circuits at the machine side the fluctuations in...

Страница 36: ...wer supply and input output signal cables pass the cables through the specified cable ports Fit a no fuse breaker conforming to European standard EN60947 2 to the source power supply of the hydraulic...

Страница 37: ...hock For the capacity for each model see 8 3 Installation of the Breaker Be sure to ground ground terminals in accordance with the law in the country concerned Make a direct connection without going t...

Страница 38: ...or cover needs to be mounted Mount it by following the procedure below 1 Engage the corners of the controller and corners of the cover together 2 Close the cover 3 Holding the grips at the left and ri...

Страница 39: ...rior cover go into the mating parts on the interior cover Check that the 7 segment display is located in the center of the display window in the operating section 5 Tighten the two screws in the lower...

Страница 40: ...is selected Power ON Normal status Only when communications option selected Communication port for maintenance Hybrid Win connection port Digital output or Ready to run Positive common Negative common...

Страница 41: ...6 OHM ELECTRIC Applicable cable outer diameter 13 to 16 2 Use a ground cable the same size as the power cable or larger 3 Connect the cables through the controller s cable port At the wiring port use...

Страница 42: ...1 Prepare a cable and cable clamp Recommended Items Cable Size Recommended Cable Recommended Cable Clamp 0 3 0 5 mm2 AWG22 20 KVC 36SB 0 3 0 5 mm2 Kuramo Electric OA W1611 OHM ELECTRIC Applicable cabl...

Страница 43: ...N2 Digital input 2 DIN3 Digital input 3 DIN4 Digital input 4 DIN5 Digital input 5 ICOM Digital input common Analog communications 2 Signal cable port 21 hole RS422 485 communications 1 Control communi...

Страница 44: ...tion Terminal Block 1 Push on the spring with e g a screwdriver Pushing in the screwdriver will open up the opening for insertion 2 Check the stripped length of the wire and insert it fully home witho...

Страница 45: ...sure to terminate shielded cables and connect them to the control communications cable grounding terminal If noise is not eliminated even when connected to the shielded cable grounding terminal make...

Страница 46: ...stop command has been input via digital input 1 STP is displayed on the panel Set the time between unit stop and unit at 0 5 seconds or more P Q selection No 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Dig...

Страница 47: ...e command flow rate command has reached the goal DO2 Digital output 2 No output OCOM Digital output common Can be either positive or negative CAUTION Prepare a DC24 V 10 0 5 A power supply externally...

Страница 48: ...ositive or negative CAUTION The switching capacity of the contact outputs is DC30 V 0 5 A at resistance load Note that driving a load exceeding the permissible current may damage the contacts or other...

Страница 49: ...s operation panel display rises after the sound of the pump running 2 Flushing operation When the starting check is completed connect all the piping except for the actuators in a loop then flush for...

Страница 50: ...ey ENT key Used to confirm selections for parameter numbers parameter settings etc 10 2 Functions of the Operation Panel 10 2 1 Function overview The operation panel has the following functions Mode D...

Страница 51: ...h momentarily Normal In the normal status the current pressure is displayed Stopped Displayed when a stop command is in effect and when the pressure is 0 15 MPa or lower AC failure This is displayed f...

Страница 52: ...n09 Reserved for the system Reserved for the system n10 Motor temperature C Displays the motor temperature n11 Radiating fin temperature C Displays the temperature of the radiating fins n12 Main circ...

Страница 53: ...rface PCB temperature C Displays the current approximate temperature inside the controller n27 Reserved for the system Displays 99 n28 to n29 Reserved for the system Displays 0 Displayed only for mode...

Страница 54: ...key or key During data number selection the display will flash 3 Confirm the data number by pressing the key The value for the selected data number will be displayed 4 Press the or key This returns yo...

Страница 55: ...key or key During data number selection the display will flash 3 Confirm the data number by pressing the key The value for the selected data number will be displayed 4 Change the set value by incremen...

Страница 56: ...hange the set values by incrementing or decrementing them with the and keys The data code will be displayed approximately 2 seconds after a set value has been changed 6 Press the key The set value wil...

Страница 57: ...isplay Parameter Name 1 Pressure setting 2 Flow rate setting 3 Acceleration time setting 4 Deceleration time setting The first digit displays the PQ selection number It is displayed in hexadecimal 0 F...

Страница 58: ...istory number selection the display will flash A00 is the latest alarm with older alarm displayed in sequence in this order A01 A02 3 Confirm the alarm history number with the key The corresponding al...

Страница 59: ...r at occurrence of the alarm 5 A u Main circuit DC voltage V DC voltage of the main circuit at occurrence of the alarm 6 A c Radiating fin temperature C Radiating fin temperature at occurrence of the...

Страница 60: ...actuation warning has occurred the L63 indication displayed on the operation panel can be retained It is also possible to record the L63 Pressure switch actuation warning in the alarm history althoug...

Страница 61: ...Warning 2 ON Normal OFF Alarm or Warning 1 0 No output Alarm or Pressure switch 1 Alarm or Pressure switch or warning P08 Working pressure of P01 Pressure switch Unit 0 or 1 Fixed value MPa 2 The rat...

Страница 62: ...1 Setting the change time when the pressure command or flow rate command is decreased at the time of switching the PQ pattern Pressure command Decrease 1MPa time Flow rate command Decrease 1000min 1 t...

Страница 63: ...arged and warning 10 Warning output P40 Unused setting items It does not affect the operation but please do not change the setting P41 PCMW Pressure coincidence detection range 0 to 99 5 Setting the p...

Страница 64: ...please do not change the setting P58 LVOL Load volume setting 0 to 18 3 This is the control gain for adjusting the response of PQ control The pressure response can be adjusted in accordance with the...

Страница 65: ...he factory default If it has been changed to indication in PSI units implement some measure to make it apparent that it is in PSI units such as affixing an indication sticker Prepare this sticker your...

Страница 66: ...Flow rate setting L min Ut Acceleration time setting sec MPa dt Deceleration time setting sec 1000min 1 The PQ selection number hexadecimal is displayed in the Pressure and flow rate characteristic c...

Страница 67: ...ing DIN2 to DIN5 the pressure and flow rate command value can be selected as shown in the following table Select the PQ selection number by digital input signal PQ selection number The parameters of t...

Страница 68: ...N Digital input 4 PQ selection 3 4 OFF ON Digital input 5 PQ selection 4 5 OFF ON PQ5 Pressure setting value PQ14 Pressure setting value PQ selection number Pressure 0 Time PQ0 PQ1 PQ0 PQ0 Pressure PQ...

Страница 69: ...d by this parameter Adjust it if you want to change pressure or flow rate and avoid the instability in switching solenoid valve Panel Indication Code Name Operation Range Default Value Unit P12 W_TM S...

Страница 70: ...et Value State of DIN1 terminal OFF ON 0 STOPS RUNS 1 RUNS STOPS 1 CAUTION Prepare a DC24 V 10 0 5 A power supply externally It is not possible to supply power from this controller to external destina...

Страница 71: ...tput the alarm statuses of this unit Connect them as necessary by following the information below Refer to the 11 5 3 Contact output and digital output selection for changing the output contents Termi...

Страница 72: ...puts alarm status and warning status OCOM Digital output common Can be either positive or negative 11 5 3 Contact output and digital output selection By changing the setting values of the parameters P...

Страница 73: ...Pressure coincidence output It will become ON when the pressure matches 6 Flow rate coincidence output It will become ON when the flow rate matches 7 Fully charged It will become ON if the main circui...

Страница 74: ...figure below Pressure Flow rate Pressure command Pressure Pressure coincidence detection range Flow rate command Flow rate Flow rate coincidence detection range Pressure and flow rate coincidence out...

Страница 75: ...ut mix 0 to 507 0 0 10PSI P02 Pressure switch output delay time 0 00 to 9 99 0 00 sec Sets the delay time from when the pressure falls below the set value for P01 Pressure switch to confirmation of th...

Страница 76: ...ay P08 Alarm output mix The setting unit of P01 Pressure switch can be selected as shown in the following table P08 Working pressure of P01 Pressure switch Unit 0 or 1 Fixed value MPa 2 The ratio of t...

Страница 77: ...control B 3 Set the parameter P58 Load Volume Setting to factory default value 3 4 Turn off the power supply of the hydraulic unit once confirm that the display on the panel turns off and turn the po...

Страница 78: ...brought into effect by turning the power off and then back on CAUTION It is necessary to turn the power on again after setting P59 PQ control method selection setting change Be sure to set P58 Load vo...

Страница 79: ...ess starting time longer it suppresses the occurrence of pressure surge Panel Indication Code Name Operation Range Default Value Unit P32 S_TM Surge less starting time 0 01 to 9 99 0 5 sec P33 L_IN Mo...

Страница 80: ...290 72 PSI P36 DR_T Dry operation judgment time 0 01 to 99 9 3 00 sec When the pressure flow rate is in the dry operation detection area shown in the figure below and P36 Dry operation judgement time...

Страница 81: ...act A contact B contact Power OFF Power ON Normal Alarm occurs 3 3 L63 Pressure switch operation 2 2 Warning occurs 1 1 It depends on the setting of P07 Warning output level setting Refer to 11 5 3 Co...

Страница 82: ...cuit failure Replace controller E08 Regenerative circuit error Regenerative resistence disconnection Replace controller Regenerative switch device failure E10 Output device error Motor control error A...

Страница 83: ...error The load torque is larger than usual Replace the motor or motor pump Sudden deceleration operation cycle is short Increase the parameter value of P13 to P28 deceleration time setting Encoder fa...

Страница 84: ...performance The motor rotation speed has risen The ambient temperature is too high E46 Board thermistor disconnection short circuit Controller interior Interface board failure Replace controller inte...

Страница 85: ...nd re set the safety valve Refer to the 12 11 Safety Valve Adjustment Instructions Replace the motor or motor pump The ambient temperature is too high Bring the ambient temperature to within the stipu...

Страница 86: ...alue set for parameter P01 Pressure switch or lower If there is nothing abnormal in the operation of the main machine review the set value for the pressure switch or the delay time 12 5 Periodic Maint...

Страница 87: ...for dust accumulation Accumulated dust will lessen the cooling effect so it should be cleaned Check if the ambient temperature has exceeded 40 C Control unit Once a month Check if the ambient tempera...

Страница 88: ...ean See 12 10 Suction Strainer Maintenance Instructions DANGER When touching the interior of the controller abide by the following procedure to prevent electric shocks 1 Shut off the source power supp...

Страница 89: ...during the work Note that oil will flow out from the piping and oil cooler during disassembly 12 7 1 Removing the oil cooler 1 Disconnect the connector for the DC fan wiring 2 Remove the hose clamps 2...

Страница 90: ...DC fan 3 Remove four cross recessed pan head screw and washer assemblies M4 10L and separate the resin shroud and core Four push rivets Use a small screwdriver etc and pull up as in to Push rivets Enl...

Страница 91: ...low wear protective glasses to avoid getting deposits and dirt in your eyes core NOTICE Take care to ensure that dirt or adhering material is not blown into the interior of the core 12 7 4 Cleaning th...

Страница 92: ...to confuse the directions of air intake exhaust of the oil cooler The wind blows from the unlabeled side to the labeled side See 6 2 1 Secure the space for air intake exhaust After completion of reass...

Страница 93: ...the figure of the filter and pulling it up to the top of the unit 12 8 2 Cleaning Air blow the filter to remove dirt or dirt that may have accumulated adhered to it WARNING When using air blow wear p...

Страница 94: ...t off the source power supply Wear protective glasses and gloves for this work 12 9 1 Removal fitting To remove it turn the cap in the counterclockwise direction by hand To fit it turn the cap in the...

Страница 95: ...oil drainage port open the oil drain plug M12 20L and drain out all of the hydraulic oil in the tank 2 Remove the four hexagonal bolts M8 20L securing the top plate and tank and hoist the strainer by...

Страница 96: ...and remove it Hexagon nut Width across flats 41 mm 12 10 2 Cleaning Air blow the suction strainer to blow off deposits and adhering material Also remove foreign matter inside the cylinder part of the...

Страница 97: ...tructions 1 Referring to the enlarged view of the safety valve on the next page loosen the lock nut Lock nut M10 width across flats of 14 mm 2 In accordance with the guidance diagram for the length of...

Страница 98: ...0 1 5 1 0 15 19 17 16 18 20 21 22 23 24 Pressure adjustment screw length Rough Diagram Lock nut Pressure adjustment screw length mm PC set pressure MPa Detail of Safety Valve Pressure adjustment scre...

Страница 99: ...Wrap sealing tape around the hexagon socket head plug Rc 1 8 and fit it as it was Mounting the fixed throttle will also change the rotational speed in the pressure holding status so adjust to the app...

Страница 100: ...speed 3 Loosen the lock nut of the throttle valve for minimum rotational speed adjustment 4 Adjust the throttle valve while monitoring the actual motor rotation speed displayed The motor rotation spee...

Страница 101: ...ix is 1 OFF ON OFF ON Power supply 3 phase Digital input Digital output OFF Approx 0 02s Unit operation Display OFF ON OFF ON OFF Approx 0 2s DIN0 start stop signal DO2 Command possible Command imposs...

Страница 102: ...tart by start stop signal Pressure control state Charge Magnetic pole detection Start by start stop signal Flow control state PQ selection 0 Power supply 3 phase Digital input DO1or2 Output selection...

Страница 103: ...ving set values makes control easier 3 Reading and saving the alarm history This is useful for speeding up the identification of parts that need maintenance and shortening stoppage times It serves as...

Страница 104: ...lic For requirements on Maintenance Repair Operation All World Machinery Supply Inc United States Daikin Group Company 6164 All World Way Roscoe IL 61073 U S A Phone 1 815 943 9111 Home Page http www...

Отзывы: