PIM00587
EN-62
Panel
Indication
Code
Name
Operation Range
Default
Value
Details
P35
DR_L
Dry operation
judgment
pressure
0.00 to 2.00 [MPa]
0.50
Sets the pressure condition for judging “E64: Dry
operation error”.
0 to 290 [PSI]
72
P36
DR_T
Dry operation
judgment time
0.01 to 9.99 [sec]
3.00
Sets the time for judging “E64: Dry operation
error”.
P37
-
Unused setting
items
-
-
It does not affect the operation, but please
do not change the setting.
P38
P_DF
Pressure
switch output
dead zone
0.00 to 1.00 [MPa]
0.50
Sets the threshold for detecting pressure recovery
from actuation of the pressure switch. Set as a
difference in the positive direction with respect to
“P01: Pressure switch”.
0 to 145 [PSI]
72
P39
DO_S
Digital output
selection
0 to 10
0
Sets the content of signals output from digital
output DO1 and alarm output AL_A.
0 : PQ number switching completion output
1 : Motor running output
2 : Reserved for the system
3 : Reserved for the system
4 : Pressure and flow rate coincidence
output
5 : Pressure coincidence output
6 : Flow rate coincidence output
7 : Fully charged
8 : Reserved for the system
9 : Fully charged and warning
10 : Warning output
P40
-
Unused setting
items
-
-
It does not affect the operation, but please
do not change the setting.
P41
PCMW
Pressure
coincidence
detection
range
0 to 99 [%]
5
Setting the pressure coincidence detection range.
Enabled when “P39: DO_S Digital output
selection” is set to 4 or 5.
P42
PCMM
The minimum
value of
pressure
coincidence
detection
0 to 99.9 [MPa]
0.1
Setting the minimum pressure of the pressure
coincidence detection.
Enabled when “P39: DO_S Digital output
selection” is set to 4 or 5.
P43
QCMW
Flow rate
coincidence
detection
range
0 to 99 [%]
5
Setting the flow rate coincidence detection range.
Enabled when “P39: DO_S Digital
output
selection” is set to 4 or 6.
P44
QCMM
The minimum
value of flow
rate
coincidence
detection
0 to 99.9 [L/min]
0.2
Setting the minimum flow rate of the pressure
coincidence detection.
Enabled when “P39: DO_S Digital output
selection” is set to 4 or
6.
P45
-
Unused setting
items
-
-
It does not affect the operation, but please
do not change the setting.
P46
-
Unused setting
items
-
-
It does not affect the operation, but please
do not change the setting.
P47
-
Unused setting
items
-
-
It does not affect the operation, but please
do not change the setting.
P48
-
Unused setting
items
-
-
It does not affect the operation, but please
do not change the setting.