PIM00587
EN-72
Digital output DO2 and contact output
Parameter
Output Signal
P08 :
Alarm output mix
P07 :
Warning output level
setting
Digital output DO2
Contact output
0 or 2
0
Alarm
ON : Normal
OFF : Alarm
Pressure switch
1
Alarm or Warning
ON : Normal
OFF : Alarm
ON OFF : Warning*
2
Alarm or Warning
ON : Normal
OFF : Alarm or Warning
1
0
No output
Alarm or Pressure switch
1 or 2
Alarm or Pressure switch or Warning
*It changes every 0.5 seconds.
Digital output DO1
P39 :
Digital output
selection
Function
Details
0
PQ number switching
completion output
When switch the PQ selection number, if the pressure command, flow
rate command reach the goal, it will become ON.
1
Motor running output
It will become ON when the motor power is on.
2
Reserved for the system
Reserved for the system
3
Reserved for the system
Reserved for the system
4
Pressure and flow rate
coincidence output
It will become ON, when the flow rate or pressure match.
5
Pressure coincidence output
It will become ON, when the pressure matches.
6
Flow rate coincidence output
It will become ON, when the flow rate matches.
7
Fully charged
It will become ON, if the main circuit is charged fully.
8
Reserved for the system
Reserved for the system
9
Fully charged and warning
It will become ON, if the main circuit is charged fully and become OFF,
when warning occurs.
10
Warning output
It will become ON, when warning occurs.
Pressure coincidence / Flow rate coincidence detection
When the digital output selection is 4, 5 or 6, the current pressure and flow rate can be detected, if the
pressure or flow rate command value is within a certain range.
The wider range of match detection range is selected by setting a percentage of the command value or
anumerical value.
Panel
Indication
Code
Name
Operation
Range
Default Value
Unit
P41
PCMW
Pressure coincidence detection range
0 to 99
5
%
P42
PCMM
The minimum value of pressure
coincidence detection
0 to 99.9
0.1
MPa
P43
QCMW
Flow rate coincidence detection range
0 to 99
5
%
P44
QCMM
The minimum value of flow rate
coincidence detection
0 to 99.9
0.2
L/min