5.5.2
65B
due to pressure
holding speed drop) alarm and L67 (pressure holding speed drop) warning status. Connect them in
accordance with the instructions below as necessary.
Terminal Name
Signal Name
Output Content: factory default setting
DOUT
Digital output
Disabled (goes OFF (closed) when ready to run)
COM1
Digital output common
Can be either positive or negative
CAUTION
Prepare a DC24 V ±10%/0.5 A power supply externally.
It is not possible to supply power from this controller to external destinations.
The maximum output current of the output circuit is 50 mA (resistance load). Note that driving a load
exceeding the permissible current may damage the circuit.
When driving inductive loads, implement surge protection measures.
Internal circuit
External power supply
(DC24 V)
(plus/minus common)
Max 50 mA
DOUT
COM1