Panel
Indication
Code
Name
Operation Range
Default
Value
Details
P57
PFD2
Pressure
attainment
signal
canceling
differential
pressure 2
0.00 to 1.00 [MPa]
0.00
Sets the differential pressure between the
pressure at which the pressure attainment
signal comes ON and the pressure at which it
goes OFF.
P58
LVOL
Load volume
setting
0 to 18
3
This is the control gain for adjusting the
response of PQ control. The pressure
response can be adjusted in accordance with
the load capacity of e.g. a hose. It is enabled
P59
NO_S
PQ control
method
selection
0: Control A
1: Control B
0
Switches the PQ control method.
Control
A
This is the specification for
general use. Normally, select
this option.
Control
B
This is the specification for
case-by-case
correspondence. Select this
option when the pressure
response needs to be
adjusted in accordance with
the hydraulic circuit.
The settings are brought into effect by
turning the power off and then back on.
CAUTION
has been changed to indication in PSI units, implement some measure to make it apparent that it is in
PSI units, such as affixing an indication sticker. Prepare this sticker yourself. Note, however, that using
the unit in PSI units in Japan is an infringement of the Measurement Act.