Connection of Input/Output Signal Cables
1.
Prepare a cable and cable clamp.
<Recommended Items>
Cable Size
Recommended Cable
Recommended Cable Clamp
0.3 - 0.5 mm
2
(AWG20 - 22)
KVC-36SB 0.3 0.5 mm
2
(Kuramo Electric)
OA-W15M-07 (OHM ELECTRIC)
Applicable cable outer diameter:
5
7
If not using input/output signals, fit a blanking cap and ensure the protection class is satisfied.
<Recommended Product> SANKEI MANUFACTURING CO. LTD. PRBG16
2.
At the cable port, use a cable clamp appropriate to ensure the port satisfies protection class IP54 or
better.
3.
Check the specifications of each signal before making the connections.
If measures against loose strands or corrosion at the end of the cable are required, use rod-type
crimp terminals with insulating cladding.
(Recommended crimp terminal: 216 322 (0.3 mm
2
), 216 221 (0.5 mm
2
), WAGO)
You are recommended to ground at one side. When grounding inside the controller, crimp a ring-
type crimp terminal with insulating cladding onto the end of the cable with a dedicated tool, and
connect it with a control/signal cable grounding screw (M4).
Signal cable port 16 hole
When RS422/485
communications option
selected
Control/communications line ground terminal