Service Diagnosis
30
C9
Description
INDOOR ROOM THERMISTOR ABNORMALITY
Supposed Cause
1. Thermistor, connector faulty.
2. Indoor PCB faulty.
Troubleshooting
Yes
Normal?
No
Yes
Normal?
# Refer thermistor resistance table.(Page 60, item 6.1)
Replace PCB.
Check thermistor resistance
value.
Check the thermistor connector
condition.
No
Replace thermistor
Correct the connection