Service Diagnosis
44
H6 (ARXN/RXN50/60M)
Description
POSITION SENSOR ABNORMAL (COMPRESSOR)
Supposed Cause
1. Compressor relay cable disconnected.
2. Compressor itself defective.
3. Outdoor PCB defective.
4. Stop valve closed.
5. Input voltage out of specifi cation.
Troubleshooting
Voltage as rated?
No
Yes
Check the power supply voltage.
Check stop valve.
Check the connection.
Turn off the power.
Check with the inverter analyzer.
Turn off the power. Disconnect
the harnesses U, V and W.
Turn on the power. Check the
electrolytic capacitor voltage.
Any LED off?
No
Correct the power supply or
replace the outdoor unit PCB.
Reconnect the electrical
components or compressor
harnesses as specified.
Electrical
components or
compressor harnesses
connected as
specified?
No
* Inverter analyzer:
RSUK0917C
Check the short circuit of the
diode bridge.
Normal?
No
Yes
Replace the outdoor unit PCB.
320 = 50 VDC?
No
Yes
Yes
Replace the outdoor unit PCB.
Correct the power supply.
OK?
No
Yes
Yes
Replace the stop valve.
Replace the compressor.
*Remark:
Refer to Appendix A for Diode bridge short circuit check procedures.(Page 66, item 6.9)
Refer to Appendix A for Inverter analyzer check. (Page 63, item 6.8)
Содержание ARXN25MV1B
Страница 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Страница 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Страница 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Страница 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...