Service Diagnosis
39
F6
Description
HEAT EXCHANGER OVERHEAT
Supposed Cause
1. The installation space is not large enough.
2. Faulty outdoor fan motor.
3. Faulty
EXV.
4. Faulty outdoor heat exchanger thermistor.
5. Faulty stop valve.
6. Dirty heat exchanger.
7. Unit
overcharge.
8. Defective outdoor unit PCB.
Troubleshooting
Check the
outdoor fan.
Check the
electronic expansion
valve.
Malfunction
Check the installation space.
Replace the outdoor heat
exchanger thermistor.
Malfunction
Replace the outdoor unit PCB.
Check the
installation
condition.
Functioning
Functioning
Functioning
Functioning
Malfunction
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit PCB.
Check the
outdoor heat exchanger
thermistor.
Malfunction
*Remark:
Refer to Appendix A for thermistor resistance checking procedures.(Page 59, item 6.1)
Refer to Appendix A for Electronic Expansion Valve (EXV) checking procedures. (Page 60, item 6.2)
Refer to Appendix A for Inverter unit refrigerant check procedures. (Page 62, item 6.4)
Refer to Appendix A for Installation condition check. (Page 65, item 6.7)
Содержание ARXN25MV1B
Страница 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Страница 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Страница 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Страница 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...