Service Diagnosis
32
E5 (ARXN/RXN_M,RXB50/60B,ARXN/RXN25/35L)
Description
COMPRESSOR OVERLOAD
Supposed Cause
1. Refrigerant
Shortage.
2. 4 way valve malfunction.
3. Stop valve malfunction.
4. Outdoor unit PCB defective.
5. Water mixed in refrigerant.
6. Electronic expansion valve defective.
7. Disconnection of discharge pipe thermistor.
8. Faulty discharge pipe thermistor.
9. Disconnection of connector S40.
10. Electronic expansion valve or coil malfunction.
11. Disconnection of 2 terminals of OL.
Troubleshooting
No
Yes
Malfunction?
Malfunction?
Yes
No
Yes
Yes
Thermistor
resistance normal?
Disconnect connector
S40 from PCB.
Replace electronic expansion or the coil.
Discharge pipe
thermistor
disconnected?
No
Yes
Insert thermistor in position.
Check resistance of 2 terminals
connector S40.
Malfunction?
Resistance between
2
WHUPLQDOVLV"
Disconnect 2 terminals of OL.
Replace outdoor PCB.
No
# Refer to thermistor resistance table.(Page 60, item 6.1)
Replace thermistor.
Refer refrigerant line
check procedures.
Connectors
properly
connected?
Yes
Check electronic expansion.
Replace four way valve or
the coil.
Replace outdoor PCB.
No
Check four way valve.
Check refrigerant line.
Connect back the connectors.
Disconnect 2
terminals of OL.
Disconnect 2
terminals of OL.
No
Yes
"
No
No
Yes
Yes
*Remark:
Please refer to Appendix A for Electronic expansion valve (page 60,item 6.2), four way valve (page 60,item
6.3) and refrigerant line checking procedures (page 62,item 6.4).
Содержание ARXN25MV1B
Страница 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Страница 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Страница 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Страница 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...