Function & Control
20
2.15 Defrost Cycle
During defrost
All models
Compressor
ON
4-way valve
OFF
EXV in operation room
Fixed opening
Outdoor fan
OFF
Indoor fan
OFF
Condition for entering defrost
• Compressor minimum run time – 6 minutes OR
• Compressor accumulated run time of 45 minutes if Outdoor coil < 3°C.
Condition for terminating defrost
• OD coil > 12°C or
• Total defrost timer of 650 seconds.
2.16 Indoor Coil Freeze Prevention
Only available in cooling mode.
When the indoor coil temperature < 2°C, the compressor starts to drop the frequency.
This protection will cut in when:
• Indoor coil temperature < 0°C for more than 180s. Compressor will stop, OD fan stop after 30s and
indoor fan can only run at lowest fan speed.
The unit can only be restarted after 3 minutes.
When the indoor coil temperature > 13°C, the compressor frequency will be reset based on the OD ambient,
room and set temperature.
2.17 High Pressure Protection
To prevent high pressure in the system.
Compressor operating frequency is adjusted based on upper limit of coil temperature.
Upper Limit Coil
Temperature
Compressor frequency
A
64°C
B
C
The compressor frequency is adjusted based on coil temperature:
• During cooling mode : outdoor coil temperature.
• During heating mode : indoor coil temperature.
This protection is activated when the coil temperature > 64°C, the compressor stop and OD fan stop after
30s.The unit can only be restarted after 3 minutes.
Содержание ARXN25MV1B
Страница 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Страница 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Страница 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Страница 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...