Function & Control
21
2.18 Discharge Pipe Temperature Control
Used as a measure of the compressor’s internal temperature.
Compressor frequency is control to keep this temperature from going up further when it rises above a certain
level.
Discharge temperature
Stop zone
Drop zone
Frequency
keep zone
Reset zone
110°C
102°C
99°C
90°C
If compressor discharge temperature > 102°C for the
fi
rst time, this control starts and set the current
frequency as upper limit. At the same time, running frequency start to reduce by 1 step and so on, until
temperature falls between 99°C and 90°C at the maintain zone.
This protection is activated when the compressor discharge temperature > 110°C. The compressor will stop
and considered trip.
If the compressor discharge temperature < 90°C , the compressor frequency will be reset based on the OD
ambient, set and room temperature.
2.19 Oil Recovery Control (Applicable for ARXN/RXN50/60L)
When the compressor operates for certain duration at low frequency, the oil level in the compressor may
become low due to incomplete oil return.
To prevent damage to the compressor or compressor lock due to low oil lever.
To promote refrigerant
fl
ow to carry the oil back to the compressor.
Entering condition:
• Compressor rotation < 35 Hz, at the end of a 20 minutes timer: set lower limit rotation to 35 Hz & EXV
opening is
fi
xed at current o 50 pulse. This control is reset when rotation > 35 Hz.
Содержание ARXN25MV1B
Страница 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Страница 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Страница 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Страница 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...