![Daikin ARXN25MV1B Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/daikin/arxn25mv1b/arxn25mv1b_service-manual_501334034.webp)
Service Diagnosis
28
A5
Description
ANTIFREEZE PROTECTION OR HIGH PRESSURE CONTROL
Supposed Cause
1. Indoor
air
fi lter, heat exchanger block due to dust accumulation.
2. Indoor air short circuit.
3. Indoor coil thermistor faulty.
4. Indoor PCB faulty.
5. Fan blower dirty.
Troubleshooting
Any air short
circuit?
Does it conform
to the thermistor
resistance table?
Yes
No
Check indoor air flow.
Check intake air filter.
Check fan blower condition.
Change indoor thermistor.
Check the dust
accumulate indoor coil.
No
Yes
Change indoor PCB.
Provide sufficient air passage.
Is it very dirty?
Yes
No
Clean the air filter.
Check indoor coil
thermistor resistance.
Is it very dirty?
Yes
# Refer to thermistor resistance table.(Page 60, 6.1)
No
Clean fan blower.
Is it very dirty?
Yes
No
Clean the indoor coil.
Содержание ARXN25MV1B
Страница 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Страница 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Страница 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Страница 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...