Service Diagnosis
37
EA
Description
4 WAY VALVE ABNORMALITY
Supposed Cause
1. Thermistor
defective.
2. 4 way valve defective.
3. Outdoor PCB defective.
4. Insuffi cient gas.
5. Foreign substance mixed in refrigerant.
6. Stop valve defective.
7. Disconnect of 4 way valve coil.
Troubleshooting
$5;15;1/0a
$5;15;10
Harness
disconnected?
Check the four way
valve switching
output.
Yes
No
Check the continuity of the four
way valve coil and harness.
Disconnect the harness from
the connector.
Functioning
Correct the four way valve
coil.
Replace the four way valve
coil.
Replace the defective
thermistor(s).
Malfunction
Replace the outdoor unit PCB.
Reconnect the thermistor(s).
Reconnect the harness.
Resistance
between harnesses.
No
Yes
Any thermistor
disconnected?
Yes
No
Check the thermistors.
Malfunction
Functioning
Refer to the refrigerant
line check procedure.
Replace the four way valve
(defective or dust-clogged).
Check the
refrigerant
line.
Malfunction
Functioning
Four way valve
coil disconnected
(loose)?
No
Yes
within spec?
*Remark:
Refer to Appendix A for thermistor resistance checking procedures.(Page 59, item 6.1)
Refer to Appendix A for Four way valve performance checking procedures.(Page 61 ,item 6.2)
Refer to Appendix A for Inverter unit refrigerant check procedures.(Page 62 ,item 6.4)
Содержание ARXN25MV1B
Страница 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Страница 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Страница 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Страница 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...