Check
SiEN12-710A
146
Service Diagnosis
5. Check
5.1 How to Check
5.1.1 Fan Motor Connector Output Check
Check No.01
1. Check connector connection.
2. Check motor power supply voltage output (pins 4-7).
3. Check motor control voltage (pins 4-3).
4. Check rotation command voltage output (pins 4-2).
5. Check rotation pulse input (pins 4-1).
5.1.2 Limit Switch Continuity check
Check No.03
Remove the front grille. The limit switch is located at the left side of the drain pan assembly.
Check the continuity of the switch connection.
∗
The shutter can be opened and closed with hand. Keep the shutter open and closed all the
way for each continuity check steps.
5.1.3 Electronic Expansion Valve Check
Check No.04
Conduct the followings to check the electronic expansion valve (EV).
1. Check to see if the EV connector is correctly inserted in the PCB. Compare the EV unit and
the connector number.
2. Turn the power off and back on again, and check to see if all the EVs generate latching
sound.
3. If any of the EVs does not generate latching noise in the above step 2, disconnect that
connector and check the continuity using a tester.
Check the continuity between pins 1, 3 and 6, and between pins 2, 4 and 5. If there is no
conductivity between the pins, the EV coil is faulty.
4. If no EV generates latching sound in the above step 2, the outdoor unit PCB is faulty.
5. If the continuity is confirmed in the above step 3, mount a good coil (which generated
latching sound) in the EV unit that did not generate latching sound, and check to see if that
EV generates latching sound.
∗
If latching sound is generated, the outdoor unit PCB is faulty.
∗
If latching sound is not generated, the EV unit is faulty.
Note:
Please note that the latching sound varies depending on the valve type.
7
6
5
4
3
2
1
S1
(R3199)
Motor power supply voltage
Unused
Unused
P.0V (reference potential)
Motor control voltage (15 VDC)
Rotation command voltage (1~ 6 VDC)
Rotation pulse input
Tester
Limit switch
Forward
Upward
Shutter status
Continuity
Closed
No continuity
Open
Continuity
(Q0363)
Содержание 2MKS40FV1B
Страница 11: ...Introduction SiEN12 710A x ...
Страница 12: ...SiEN12 710A List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Страница 17: ...Heat Pump SiEN12 710A 6 List of Functions ...
Страница 25: ...Heat Pump SiEN12 710A 14 Specifications ...
Страница 33: ...Printed Circuit Board Connector Wiring Diagram SiEN12 710A 22 Printed Circuit Board Connector Wiring Diagram ...
Страница 75: ...Instruction SiEN12 710A 64 Operation Manual 2 3 Names of Parts FTKS 25 35 D FTXS 25 35 E Indoor unit ...
Страница 111: ...Instruction SiEN12 710A 100 Operation Manual ...
Страница 199: ...Wiring Diagrams SiEN12 710A 188 Appendix ...
Страница 203: ...SiEN12 710A iv Index ...