SiEN12-710A
Check
Service Diagnosis
147
Valve Body Condition (Symptom)
Check Method / Measure
(1) Valve body catches at fully opened or half
opened position.
(Symptom)
Cooling:
"
Water leakage at the no-operation unit
"
Flow noise of refrigerant in the no-operation unit
"
Operation halt due to anti-icing function
Heating:
"
The unit does not heat
"
Refrigerant flow rate vary by unit
(Discharge air temperatures are different by
room)
"
Peak cut
Reset power supply and conduct cooling
operation unit by unit.
(2) Valve body catches at complete close
position.
(Symptom)
Cooling:
"
The only unit having problem does not cool the
room .
"
When the only faulty unit is in operation, the unit
makes pump down.
(The low pressure of the unit becomes vacuum)
"
IT is activated.
"
Abnormal discharge pipe temperature
Heating:
Insufficient gas due to liquid refrigerant
stagnation inside
the faulty indoor unit
(Only for heat pump model)
"
The unit does not heat the room.
"
OL is activated.
"
Abnormal discharge pipe temperature
Reset power supply and conduct cooling
operation unit by unit.
(3) Valve does not open fully.
(Symptom)
"
The unit does not cool nor heat (only for heat
pump model.)
"
OL is actuated.
"
Abnormal discharge pipe temperature
Check the number of rotation of shaft if it is 5 and
half from full open to complete close using
manual coil for electronic expansion valve. When
the number of rotation of shaft is less than the
above value, the valve may catch anywhere of
the body.
YE
S
(R7154)
NO
Repl
a
ce the EVn of the room.
Check the li
q
u
id pipe temper
a
t
u
re
of no-oper
a
tion
u
nit.
I
s
it
a
lmo
s
t
sa
me
as
the o
u
t
s
ide
a
ir
temper
a
t
u
re?
(R7155)
Repl
a
ce the EVn of the room
YE
S
NO
Doe
s
the
pre
ssu
re
b
ecome into
v
a
c
uu
m zone?
Check the low pre
ssu
re
Содержание 2MKS40FV1B
Страница 11: ...Introduction SiEN12 710A x ...
Страница 12: ...SiEN12 710A List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Страница 17: ...Heat Pump SiEN12 710A 6 List of Functions ...
Страница 25: ...Heat Pump SiEN12 710A 14 Specifications ...
Страница 33: ...Printed Circuit Board Connector Wiring Diagram SiEN12 710A 22 Printed Circuit Board Connector Wiring Diagram ...
Страница 75: ...Instruction SiEN12 710A 64 Operation Manual 2 3 Names of Parts FTKS 25 35 D FTXS 25 35 E Indoor unit ...
Страница 111: ...Instruction SiEN12 710A 100 Operation Manual ...
Страница 199: ...Wiring Diagrams SiEN12 710A 188 Appendix ...
Страница 203: ...SiEN12 710A iv Index ...