Troubleshooting
SiEN12-710A
122
Service Diagnosis
4.11 Input Over Current Detection
Remote Control
Display
E8
Method of
Malfunction
Detection
An input over-current is detected by checking the power consumption value of outdoor unit with
the compressor running.
Malfunction
Decision
Conditions
"
The following input value (calculated from power consumption of outdoor unit) with the
compressor running continues for 2.5 seconds.
Input value : Above 15 A
Supposed
Causes
"
Over-current due to compressor failure
"
Over-current due to defective power transistor
"
Over-current due to defective inverter main circuit electrolytic capacitor
"
Over-current due to defective outdoor unit PCB
"
Error detection due to outdoor unit PCB
"
Over-current due to short-circuit