
Troubleshooting
SiEN12-710A
128
Service Diagnosis
4.15 Position Sensor Abnormality
Remote Control
Display
H6
Method of
Malfunction
Detection
A compressor startup failure is detected by checking the compressor running condition through
the position detection circuit.
Malfunction
Decision
Conditions
"
The compressor is not running in about 15 seconds after the compressor run command
signal is sent.
"
Clearing condition: Continuous run for about 11 minutes (normal)
"
The system will be shut down if the error occurs 16 times.
Supposed
Causes
"
Compressor relay cable disconnected
"
Compressor itself defective
"
Outdoor unit PCB defective
"
Stop valve closed
"
Input voltage out of specification
Содержание 2MKS40FV1B
Страница 11: ...Introduction SiEN12 710A x ...
Страница 12: ...SiEN12 710A List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Страница 17: ...Heat Pump SiEN12 710A 6 List of Functions ...
Страница 25: ...Heat Pump SiEN12 710A 14 Specifications ...
Страница 33: ...Printed Circuit Board Connector Wiring Diagram SiEN12 710A 22 Printed Circuit Board Connector Wiring Diagram ...
Страница 75: ...Instruction SiEN12 710A 64 Operation Manual 2 3 Names of Parts FTKS 25 35 D FTXS 25 35 E Indoor unit ...
Страница 111: ...Instruction SiEN12 710A 100 Operation Manual ...
Страница 199: ...Wiring Diagrams SiEN12 710A 188 Appendix ...
Страница 203: ...SiEN12 710A iv Index ...