Troubleshooting
Service Diagnosis
139
4.21 Insufficient Gas
Remote Control
Display
U0
Method of
Malfunction
Detection
Gas shortage detection I :
A gas shortage is detected by checking the power consumption value and the compressor
running frequency.
Malfunction
Decision
Conditions
Gas shortage detection I :
Power consumption < 4578 / 256 (W/Hz) × Compressor running frequency – 638 (W)
However, when the status of running frequency > 48 (Hz) is kept on for a certain time.
If a gas shortage error takes place 4 times successively, the system will be shut down. The error
counter will reset itself if this or any other error does not occur during the following 60-minute
compressor running time (total time).
Supposed
Causes
"
Refrigerant shortage (refrigerant leakage)
"
Poor compression performance of compressor
"
Stop valve closed
"
Electronic expansion valve defective