
SiEN12-710A
Troubleshooting
Service Diagnosis
125
4.13 High Pressure Control in Cooling
Remote Control
Display
F6
Method of
Malfunction
Detection
High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the
temperature being sensed by the heat exchanger thermistor exceeds the limit.
Malfunction
Decision
Conditions
"
Activated when the temperature being sensed by the heat exchanger thermistor rises above
65°C.
"
Deactivated when the temperature drops below 53°C.
Supposed
Causes
"
The installation space is not large enough.
"
Faulty outdoor unit fan
"
Faulty electronic expansion valve
"
Faulty outdoor unit heat exchanger thermistor
"
Faulty outdoor unit PCB
"
Faulty stop valve
"
Dirty heat exchanger
Содержание 2MKS40FV1B
Страница 11: ...Introduction SiEN12 710A x ...
Страница 12: ...SiEN12 710A List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Страница 17: ...Heat Pump SiEN12 710A 6 List of Functions ...
Страница 25: ...Heat Pump SiEN12 710A 14 Specifications ...
Страница 33: ...Printed Circuit Board Connector Wiring Diagram SiEN12 710A 22 Printed Circuit Board Connector Wiring Diagram ...
Страница 75: ...Instruction SiEN12 710A 64 Operation Manual 2 3 Names of Parts FTKS 25 35 D FTXS 25 35 E Indoor unit ...
Страница 111: ...Instruction SiEN12 710A 100 Operation Manual ...
Страница 199: ...Wiring Diagrams SiEN12 710A 188 Appendix ...
Страница 203: ...SiEN12 710A iv Index ...