47
2.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
40 class 50 class
FCG 3
90
85
FCG 2
72
70
FCG 1
62
55
TCG 1
140
150
TCG 2
180
180
TCG 3
300
300
Frequency
FCG3
FCG2
FCG1
TCG1sec
TCG2sec
TCG3sec
Time