CTC EcoZenith
I
550
HP1 (2, 3), alarm disch.°C
The highest discharge gas temperature the compressor is allowed to deliver.
Factory value 127°C (setting 110-130°C).
HP1 (2, 3), max brine in °C
Shown only when the heat pump type is set to EcoPart. The highest allowed
temperature from a bore hole/ground loop. Factory value 20°C (setting -15 to 20°C).
HP1 (2, 3), min brine in °C
Shown only when the heat pump type is set to EcoPart. The lowest allowed
temperature from a bore hole/ground loop. Factory value -5°C (setting -5 to 30°C).
HP1 (2, 3), max diff br. °C
Shown only when the heat pump type is set to EcoPart. The highest allowed
temperature difference between in- and outgoing brine liquid. During the first
72 operating hours, a further 2°C difference is allowed. Factory value 7°C
(setting 0-7°C).
Diff HP upper °C
The allowed temperature difference that the actual value for the upper tank is allowed
to be below the reference value before tank charging with the heat pump starts.
Factory value 5°C (setting 1-20°C).
Diff HP lower °C
The allowed temperature difference that the actual value for the lower tank is allowed
to be below the reference value before tank charging with the heat pump starts.
Factory value 5°C (setting 1-20°C).
Start delay
The delay which prevents compressor start earlier than 10 min after compressor stop.
The delay is also activated at power failure or the first time the heat pump is started.
Factory value 10 minutes (setting 10-60 minutes).
Temp. Log
Contains values intended for service personnel.