For the property owner

56

CTC EcoZenith 

I

 550 

dT setpoint low °C

Setting of the number of degrees that the lower tank of the CTC EcoZenith 

I

 550 

must exceed its reference value to start transfer to the external buffer tank. This 
setting applies to charging of solar energy when a heating need is present on the 
radiator system.
Factory value 7°C (setting 2-50°C).

HP charging

Charging the external buffer tank with heat from the heat pump is especially 
interesting when there are different power rates during the day. The buffer tank(s) 
can then be charged when the power rate is low. The lower tank of the CTC 
EcoZenith 

I

 550 will work towards the set temperature during those periods which 

are scheduled in the “Day by Day” menu and then transfer heated radiator water 
to the buffer tank(s), provided that it has a lower temperature. Factory value Off 
(setting Off, 20-60°C).

Week prog.

In this menu the charging of the external tank is scheduled.

Week program Menu

(Installer/Settings/Ext storage tank/ Week porg.

)

In this menu the charging of the external storage tanks during the weekdays 
is scheduled. The schedule is repeated every week. The illustration shows 
the factory values to be changed.

 = External storage tank charging is started at the time indicated after the arrow.

 =  External storage tank charging is interrupted at the time indicated after 

the arrow.

Example

Mon 

-

On Monday morning between 06:00 and 07:00 external storage tank charging 
is carried out. No charging takes place at other times.

Week prog.
Mon  

6

7

-

-

Tue 

6

7

-

-

Wed  

6

7

-

-

Thu 

6

7

-

-

Fri 

6

7

-

-

Sat 

7

8

-

-

Sun 

7

8

-

-

Pool Menu

(Installer/Settings/Pool)

In this menu settings for the pool operation are made

Pool temp °C

Stop temperature for the pool: at this set temperature the charging of the pool 
is halted. Factory value 22°C (setting 5-50°C).

Pool diff °C

This value indicates how much the temperature is allowed to fall below the 
“Pool temp °C” before the charging of the pool starts again. Factory value 1.0°C 
(setting 0.2-5.0°C).

Pool priority

“High”  The pool is allowed to take so much heat that additional heat is activated.
“Low”  The pool is not heated when additional heat is activated.
Factory value High (setting High/Low).

Pool
Pool temp °C  

22

Pool diff °C 

1.0

Pool priority 

 high

The “Lower tank min” menu 
should not be set to a lower value 
that the “Pool temp” menu.

Содержание EcoZenith I 550

Страница 1: ...Installation and Maintenance Manual CTC EcoZenith I 550 for the property owner 161 505 71 1 2010 03 21...

Страница 2: ...data 36 Stored operating data Menu 40 Night reduction 41 Week program Menu 42 Block Menu 42 Installer Menu 43 Settings Menu 43 Radiator System Menu 45 Heat Pump Menu 46 Electric heater Menu 47 Upper T...

Страница 3: ...r individual settings indicates desired values for instance temperatures and energy consumption facilitates settings in a simple and structured manner Your CTC EcoZenith I 550 has built in finned copp...

Страница 4: ...stic roof Please refer to the section Transport unpacking and installation in the part for the installation engineer The CTC EcoZenith I 550 should not be lowered below floor level Safety Instructions...

Страница 5: ...5 For the property owner CTC EcoZenith I 550...

Страница 6: ...ks according to the outside temperature only During the adjustment period it is important that the night reduction function not be selected all thermostat valves on the radiators be fully opened the o...

Страница 7: ...ifferent outside temperatures Primary Flow Temperature Primary Flow Temperature The value of the slope that has been set is the primary flow temperature when the outside temperature is 15 C Outside Te...

Страница 8: ...ees If the inside temperature is too cold increase the value at Inclination by a couple of degrees Then wait 24 hours before the next adjustment If the inside temperature is too warm decrease the valu...

Страница 9: ...ke of the operating economy this means that the lower tank of the CTC EcoZenith I 550 which works towards the radiator needs should have as low a temperature as possible A floor heating system uses lo...

Страница 10: ...water tank The CTC EcoZenith I 550 is prepared for this and provides the possibility to utilize heat pump energy to heat the extra domestic hot water tank This means that there is a large buffer with...

Страница 11: ...nnections are placed symmetrically on both sides of the tank Insulation The tank is insulated by 90 mm thick molded polyurethane foam for minimum heat loss Lower Tank Connections The heat pump and sol...

Страница 12: ...oZenith The control is specially adapted for controlling CTC s heat pumps solar panels wood boilers additional boilers water heating buffer tanks etc The EcoZenith is well insulated with 90 mm PUR and...

Страница 13: ...reads the current inside temperature and can adjust the heat for instance when it is windy outside and the house loses heat The outdoor sensor does not sense this When the sun is shining in or in othe...

Страница 14: ...mous heat conduction area since the copper coil is finned on the inside as well as the outside For more information on settings and tips please se the Hot Water section Hot Water Circulation See also...

Страница 15: ...ting takes place in the upper tank This means that with a high upper tank temperature an ample hot water supply is obtained The stop temperature in the upper tank is factory set at 50 C which means th...

Страница 16: ...ature to the heating system is needed but during winter a higher temperature is needed to maintain the desired inside temperature The savings of a heat pump is directly connected to the COP value COP...

Страница 17: ...30 minutes Different Heat Pumps See also Heat pump Menu in the Detail Description Menus Installer Settings Heat pump 1 2 3 section The CTC EcoZenith I 550 can control different types of heat pumps e g...

Страница 18: ...st start as anti freeze when an air water heat pump is installed If a speed controlled charge pump is installed the pump will only work at 25 of its maximum capacity This provides for increased saving...

Страница 19: ...riority is selected the external additional boiler is activated before the immersion heater s when low priority is selected the immersion heater s is activated first After a certain delay which is fac...

Страница 20: ...d controlled pump controls the flow in order always to deliver 7 degrees higher temperature This means that if the effect in the panel increases the charge pump will increase the flow and if the effec...

Страница 21: ...circuit has fallen to 30 C the charging is stopped If the brine circuit becomes warmer than the factory set 18 C the recharging will also be stopped since it then becomes too high a temperature for t...

Страница 22: ...water is stored below 60 C heating at regular intervals is necessary to eliminate the risk of Legionella This function is built into the EcoZenith I 550 which first heats the upper tank as much as it...

Страница 23: ...ek prog The CTC EcoZenith I 550 can be connected to one or several buffer tanks This is mainly used when connecting wood and solar energy systems where the volume in the CTC EcoZenith I 550 is not suf...

Страница 24: ...ransfer starts at 80 degrees and stops at 77 degrees The lower tank must be at least 7 degrees warmer than the buffer tank for the charging to be allowed to start This applies independently of heating...

Страница 25: ...than the buffer tank for the charging to be allowed to start according to factory set values Recharging from Buffer Tank to EcoZenith Recharging from the buffer tank s to the CTC EcoZenith I 550 is a...

Страница 26: ...sing the Buttons You can easily enter the different menus to find information on the operation or to set your own values The function of the different buttons is described below A The display window B...

Страница 27: ...ursor is moved with the increase and decrease button D The cursor is blackened when a line is selected Push the undo button B to deselect 3 Indication more lines The arrow indicates that there are mor...

Страница 28: ...a Total oper time h 8768 El heat kWh 22375 Max primary flow C 55 Total oper time h HP1 2935 Oper time 24h HP1 10 22 Starts 24h HP1 14 Energy KWh 24672 Total oper time h HP2 2935 Oper time 24h HP2 4 12...

Страница 29: ...t extraDHW C 60 Charge pump min 50 Charge pump max 100 Run time DHWcirc 4 Time DHWcirc 15 Week pr DHWcirc Ext DHWdiff C 5 Add DHWdays 14 Solar Energy dT max solar C 7 dT min solar C 3 Min rpm pump 30...

Страница 30: ...Sensor 81 Active Sensor 87 Active Def Heat pump 1 Heat pump 05 No Type EcoAir Charge pump 31 0 10V 3 valve 54 Active 3 valve 55 Active Def Heat pump 2 Heat pump 06 No Type EcoAir Charge pump 32 0 10V...

Страница 31: ...C 7 Diff HP upper C 5 Diff HP lower C 5 Start delay 10 Temp Log Test radiator system Mixing valve1 59 Rad pump1 36 Off Mixing valve2 60 Rad pump2 37 Off Mixing valve3 57 Rad pump3 35 Off Room Sensor...

Страница 32: ...in the respective menu for room temperature only Upper tank C The highest temperature of the product is displayed here Its sensor is placed in the upper part of the tank Display only EcoZenith Mon 12...

Страница 33: ...staller This menu contains three submenus one menu for default settings to be made one for defining which subsystems and components the current heating system consists of and one menu for service pers...

Страница 34: ...ystems which have been defined in the Installer Define application menu The reference value can be changed with the Up Down arrow For night reduction NR is displayed in the upper right corner If only...

Страница 35: ...so increased in accordance with values set in the Installer Settings Upper Tank menu at the time indicated after the arrow the DHW capacity is reduced to normal setting at the time indicated after the...

Страница 36: ...s its maximum operation temperature during the charging of the upper tank The reference value is not reduced during the Min temp upper Diff HP upper menu Lower tank C The temperature in the lower part...

Страница 37: ...is either blocked in the settings menu or not allowed due to outside temperature being too low concerns EcoAir the outside temperature is then shown simultaneously If more than one heat pump 2 3 is d...

Страница 38: ...dicates in which mode the diverting valve for external tank charging 56 is set Up or Down In the Up mode heat can be charged from an external buffer tank to the upper part of the CTC EcoZenith I 550 a...

Страница 39: ...pper part of the tank additional heat This line shows the time remaining of the countdown to 0 The value can be set 0 240 min and then the mixing valve can be blocked so that it never takes heat from...

Страница 40: ...y Starts 24h HP1 2 3 The number of starts the compressor has made during the last 24 hours A new value is stored shown once every 24 hours After the initial start the value is shown after 24h only Ene...

Страница 41: ...ty of two reductions per day The schedule is repeated every week Block means scheduling reductions during several days of the week e g Monday to Friday Two reduction periods can be scheduled The sched...

Страница 42: ...weekdays are scheduled The schedule is repeated every week The illustration shows factory values which can be changed If more reduction periods are required the intermediate times should be programme...

Страница 43: ...ngs only Settings Language English Radiator system 1 Radiator system 2 Radiator system 3 Heat pump 1 Heat pump 2 Heat pump 3 Elec heater Upper Tank Lower Tank Solar Energy Wood Boiler Ext Boiler Ext s...

Страница 44: ...ture and difference for the pool operation can be set here if applicable Remote control Choice of remote control type NR Remote night reduction e g via the minicall system RC Ripple control Disconnect...

Страница 45: ...ry day to avoid seizure The system starts again automatically when heat is needed Factory value 16 C setting 10 30 C Heat Off time When the outside temperature falls to the limit at which heat is need...

Страница 46: ...mary flow menu is obtained During the next 10 days the flow temperature is constant according to the Max primary flow menu Thereafter the primary flow is reduced by 5 degrees per day again until the t...

Страница 47: ...r water Applies to speed controlled pumps only Factory setting 50 setting 20 100 Settings below 25 are not recommended HP1 2 3 charge pump max Here you set the maximum speed in percent for the circula...

Страница 48: ...of warm water need A longer set time means that heat is prioritized for a longer period Applies only when a heat pump is connected Factory value 40 min setting 10 120 min Upper Tank Stop Temp C 50 Max...

Страница 49: ...5 C setting 35 55 C Addheat upp tank C Stop temperature for additional heat from immersion heater s Is used when the CTC EcoZenith I 550 is in additional heating status when no heat from the heat pump...

Страница 50: ...and is stopped at 22 00 There is no domestic hot water circulation at other times Example 2 Sat 7 22 The DHW circulation operates between 07 00 and 22 00 on Saturdays Week pr DHWcirc Mon 5 8 16 22 Tue...

Страница 51: ...irculating pump for the solar panels stops and the solar energy charge to the lower tank is finished Factory value 3 C setting 2 20 C Min rpm pump Here you set the min permissible rpm in percentage fo...

Страница 52: ...e interval for graph Factory value 1 h setting 1 48 h Flow l min Setting of flow for the solar panels circulating pump For information on measuring of the flow see the Installation and Maintenance Man...

Страница 53: ...frost protection function is activated Factory value 25 C setting 30 to 7 C Calibration Sensors Menu Installer Settings Solar Calibration sensors Here the sensor temperatures can be corrected From so...

Страница 54: ...add heat Here is indicated if the product is connected to a rate controlled grid When the heat pump is turned off by the grid the external boiler should activate This does not apply in Sweden Factory...

Страница 55: ...0 and the upper part of the external buffer tank which controls the conditions for halting the recharging from the external buffer tank to the upper tank in the CTC EcoZenith I 550 Factory value 3 C s...

Страница 56: ...ge tanks during the weekdays is scheduled The schedule is repeated every week The illustration shows the factory values to be changed External storage tank charging is started at the time indicated af...

Страница 57: ...ich and how many immersion heaters are used Solar Energy The settings for the solar energy are which type of solar collector is used if bore holes energy wells that should be reloaded with solar energ...

Страница 58: ...system 1 Yes Room sensor 1 No 4 valve 59 Active Rad pump 36 Active Sensor 79 Active Sensor 81 Active Sensor 84 Active Define Radiator System 2 Menu Installer Define application Def Radiator system 2...

Страница 59: ...sor 74 Active Sensor 81 Active Sensor 87 Active Define Heat Pump 1 Menu Installer Define application Def Heat pump 1 Heat pump 05 Here you select if heat pump 1 05 is included in the operation The fac...

Страница 60: ...enu lines are shown underneath These are turned off at the setting No Note that the setting locally in heat pump 3 07 should be A3 Thus this setting is made in the heat pump s own control Type The typ...

Страница 61: ...s is the sensor which reads the temperature into the solar collectors Charge pump 30 Indication that charge pump 30 is activated This is the circulating pump which pumps non freeze heat carrier liquid...

Страница 62: ...Sensor 85 Indication that sensor 85 is activated This sensor reads the temperature incoming to the CTC EcoZenith I 550 from the water coming from the external additional boiler Charge pump 34 Indicati...

Страница 63: ...ith domestic hot water circulation are defined The factory setting is No When the setting is Yes the menu lines are shown underneath These are turned off at the setting No ExternalDHWtank If there is...

Страница 64: ...Heat pump 1 Heat pump 2 Heat pump 3 Valves Elec heater Solar Energy Wood Boiler Ext Boiler Ext storage tank Hot water Pool Function Test Menu Installer Function test In the Function test menu the inst...

Страница 65: ...diff br C 7 HP2 max primary C HP2 max return C HP2 alarm disch C 127 HP2 max brine in C 20 HP2 min brine in C 5 HP2 max diff br C 7 HP3 max primary C HP3 max return C HP3 alarm disch C 127 HP3 max bri...

Страница 66: ...n in and outgoing brine liquid During the first 72 operating hours a further 2 C difference is allowed Factory value 7 C setting 0 7 C Diff HP upper C The allowed temperature difference that the actua...

Страница 67: ...upply to the tank during drainage The drain valve is packaged separately and can be connected directly onto one of the lower connections if one is free or to a low lying pipe When draining the whole s...

Страница 68: ...in other parts of the house The room sensor can then be deselected temporarily during the burning The CTC EcoZenith I 550 will then provide the radiators with heat according to the set heating curve s...

Страница 69: ...et Increase if needed More on this in the Heating Curve section also see the Installer Settings Radiator System 1 2 and 3 menu that the temperature set back is not maladjusted that the mixing valve is...

Страница 70: ...f the fuse size in the house is correct Sound Problems Sudden pressure changes in the tap water system may cause noise This is due to pressure surges which occur when for instance an older type of ins...

Страница 71: ...urned off due to the supply low rate not beingalive This text is shown only when the Electr Tariff menu is set to Yes Tariff add heat On This text is shown only if the external boiler is on due to the...

Страница 72: ...Flue Gas 73 Sensor Pool Temp 88 Information Text Description Communicat error display This text is shown when the communication between the display board and relay board is not working Communicat err...

Страница 73: ...hifted The power to the system must be cut in order to correct this fault A1 A2 A3 sensor outside A faulty not connected or shorted sensor and a value outside the sensor s range triggers alarm If it i...

Страница 74: ...p 65 55 C electric power 24 kW allowed l 523 Pressure differential at flow 40 l min bar 0 7 Volume tank l 540 Volume domestic hot water coil l 11 4 Max operating pressure tank bar 2 5 Max operating pr...

Страница 75: ...inside 2 Expansion vessel Top con Lifting socket G 1 1 4 inside 3 Solar coil 18 mm 4 Cold water 22 mm 5 Domestic hot water 22 mm 6 Domestic hot water circulation 22 mm 7 Radiator primary flow spring...

Страница 76: ...his declaration relates is in conformity with requirements of the following directiv auf das sich diese Erkl rung bezieht konform ist mit den Anforderungen der Richtlinie EC directive on Pressure Equi...

Отзывы: