Page33
10. Specifications
Power Capacity(KVA)
1000(950w)
1400va (1120w)
1800va
(1440w)
2200va
(1540w)
3000va
(2520w)RM
Topology
Synthetic power On-line UPS
Isolation transformer
Provides a galvanic isolation while operating the inverter operating
Recharge time(normal)
8 hours
Extended Battery Option
Yes(PowerCell Guard)
Typical transfer time with load
2msec(Synthetic power On-line UPS)
Input Specification
Nominal input voltage and Frequency range
1 phase 200/220/230(user’s require)Voltage
±
20% / Frequency 50/60 HZ
±
5%
Output Specification
Nominal output voltage
1 phase 200/22/230 Dip switch selectable
Output voltage regulation
(Auto Boost & Auto Trim)
Normal 10% / On line 3%
Output voltage waveform
Sine wave
Load crest factor supported(c.f)
Up to 5 : 1
Power factor tolerance
Loads with 0.5 to 1.0 power factor
Efficiency inverter at full load
>95%
Audible noise(front 1.5m away)
43 Dba
Overload capacity
Up to 110% for 10 seconds then transfer to inverter
Internal power distribution unit(PDU)
2 and 4 plugs
Feature
Runtime(Battery)Expandability Yes(PowerCell
Guard)
User serviceable (SNMP Service)
Quick SNMP & OTERS Win95/Win98)
Indicators, Interface & control
LED Indicators
Load level(25-100%), Battery level(25-100%, Auto Boost & Auto Trim, Inverter,
Battery abnormal, Alarm, Input voltage level(5 grade)
Power cord
Yes
Intelligent serial interface
(O/S management protocol)SNMP
Yes(Quick SNMP & Power Mon II & SmartMon & Others GUI Protocol)
Others
DC Characteristics
27 – 39V
Battery type
Lead-acid maintenance free & user’s optional