Telnet protocol
In firmware version 1.34 Telnet protocol has been replaced with expanded version of SNMP
protocol. If there is a need to use the Telnet protocol, you should downgrade firmware to version
1.32 (section 3.5). Both the firmware can be found on the website: www.creotech.pl
Firmware 1.32 – Basic SNMP and Telnet
Firmware 1.34 and higher – Expanded SNMP and no Telnet
IP Power strip can be operated from the telnet protocol. Connection parameters are:
IP Address: previously set IP address of the IP power strip
Port number: 23
Below is a table with a list of commands.
Description
Command
Status
output show
output on [output number] <
delay >
output off [output number] <
delay >
Configuring the network
interface parameters
config dhcp <on/off>
config ip <ip adress>
config mask <
network mask >
config gateway <
default gateway>
Setting the default output
states
config output <111111>
Setting the friendly name
config outputname [output number] <name>
Configuring the watchdog
watchdog [output number] <ip adress>
Setting up user accounts
usermod [uid] <[r/w/-]
[r/w/-]
[r/w/-]
[r/w/-]
[r/w/-]
[r/w/-]> <user name> < password >
Show serial number
serial
Changing the password
passwd
Save the configuration
save
Reset the IP power strip
reset
Closing of the session
exit