76
60T - 280T
COSMOGAS
17.14 - Temperature and water
measurement probes
There are various temperature sensors on the exchanger
body. The electrical resistance between the two sensor
contacts must match what is shown in figure 17-13.
The temperature probes are:
1001
,
1002
,
1006
and
1007
Figure 17-13 - Water sensor curve
Figure 17-14 - External temperature sensor curve
17 - MAINTENANCE
17.15 - External temperature probe
The
1004
external temperature sensor (see section 13.1.4)
comes standard. The electrical resistance between the two
sensor contacts must match what is shown in figure 17-14.