59
60T - 280T
COSMOGAS
16 - USE
16.1
3
- “User menu”
Pressing the RESET key for 2 seconds accesses the “user
menu”. Display “M” in figure 16-1 begins to show parameter
1001
to tell the user that the mode has changed.
Using the and keys, you can scroll through
the parameters in the menu.
To exit the menu, simply press the RESET key again for 2
seconds.
Parameter
Parameter description
U.M.
1001
Burner 1 - Water supply temperature
°C
1002
Hot water storage tank temperature (if present)
°C
1004
External temperature (visible when an external temperature sensor is installed)
°C
1006
Burner 1 - Flue gas temperature
°C
1007
Burner 1 - Return temperature
°C
1008
Burner 1 - Ionisation current
uA
1009
Burner 1 - Main circuit pump and motorised valve status
ON/OFF
1010
Heating circuit pump status
ON/OFF
1011
Domestic hot water circuit pump status
ON/OFF
1012
Calculated heating setpoint (with external probe enabled)
(only for 60T and 70T models. See Parameter 1107 for the other models)
°C
1040
Burner 1 - Current fan rotation speed
rpm
1041
Burner 1 - Fan rotation speed at ignition
rpm
1042
Burner 1 - Fan rotation speed at minimum output heat
rpm
1043
Burner 1 - Fan rotation speed at maximum output heat
rpm
1051
Burner 1 - Last recorded lock-up (Loc) (see section 16.16.1) (255 means no block)
/
1052
Burner 1 - Last recorded error (Err) (see section 16.16.2) (255 means no error)
/
1053
Burner 1 - Number of times the burner lost its flame
No.
1055
Burner 1 - Number of failed burner ignitions
No.
1056
Burner 1 - Number of hours worked
h x 10
1057
Burner 1 - Number of hours worked in domestic water with hot water storage tank
h x 10
1059
*
interval of time between the last two errors (Err)
1
value in minutes;
2
value in hours;
3
value in days;
4
value in weeks;
1060
*
interval of time between the last two lock-ups (Loc)
1062
Burner 1 - Water flow rate
l/min
1101
Multi-burner: Number of burners on
No.
1102
Multi-burner: Manifold temperature
°C
1103
Multi-burner: Number of burners locked (Loc)
No.
1104
Multi-burner: Number of burners in Error (Err)
No.
1106
Multi-burner: Appliance in emergency
Yes/No
1107
Multi-burner: Calculated heating setpoint
only 100T, 115T, 140T, 210T and 280T models) (see Parameter 1012 for the other models)
°C
1120
Multi-burner: Burner 1 modulation level
%
1121
Multi-burner: Burner 2 modulation level
%
1122
Multi-burner: Burner 3 modulation level
%
1123
Multi-burner: Burner 4 modulation level
%
If no keys are pressed for more than 60 seconds, it
automatically exits the menu.
For models from 100T to 280T, all the parameters indicated as
“Burner 1” refer to the appliance Master Burner. To display the
same parameters for the other burners, you must connect the
display to the burner in question as described in section 17.8.
The following parameters can be accessed in this menu:
*
How to read the values of parameters 1059 and 1060:
i.e.: If it shows 1:29, it means 29 minutes;
i.e.: If it shows 2:12, it means 12 hours;
i.e.: If it shows 3:15, it means 15 days;
i.e.: If it shows 4:26, it means 26 weeks.