15 - COMMISSIONING
15.1 - Commissioning
Before commissioning the appliance, the following operations
must be done.
15.1.1 - User instructions
Instruct the user on how to properly use the appliance and
the entire system in general. In particular:
Give the user the use and installation manual and all the
documents contained in the packaging.
Teach the user about the special measures for the flue
exhaust, informing them that they must not be modified.
Inform the user of the necessary water pressure control
in the system and of the necessary measures to fill and
bleed air.
Inform the user about properly adjusting temperatures,
control units/room thermostats and radiators for energy
saving.
15.1.2 - Filling the condensate drain
siphon
The siphon located inside the appliance must be filled with
water to create the stop that can prevent flue gases from
escaping out of duct “5” in figures 3-3, 3-5 and 3-7.
To this end, proceed as follows:
(refer to figure 15-1)
1.- unscrew and remove plug “A” shown in the figure;
2.- put a rubber hose into opening “S” and position a funnel
at the other end of the hose;
3.- slowly pour about 5 litres of water though the funnel;
4.- reassemble everything in reverse order.
15-1 - Filling the condensate drain siphon
ATTENTION!!! If the boiler stays off for more than
3 months, the siphon must be filled again as explained
above.
ATTENTION!!! Once the appliance has been
started up again, make sure no flue gases are escaping
from plug “A”.
15.1.3 - Filling the heating system
When the appliance is being powered, if
Err 59
appears on the display, it means that the system needs to
be filled. Proceed as follows:
only use clean water from the water mains.
ATTENTION!!! Chemicals like antifreeze must
be added as per the instructions on the product. In any
case, said substances must not be put directly into the
boiler.
ATTENTION!!! for water heaters, adding
chemicals like antifreeze is absolutely prohibited.
Failure to follow this provision could cause serious
harm to human health or even death.
1.- open the air bleed valve (part “35” in figure 3-7)
2.- open the filling device provided for by the installer
upstream of the appliance and fill the system until the
manometer detects a pressure of 1,5 bar, shown on the
display (part “M” in figure 16-1) (
Err 59
appears on
the display); If you wish to increase the filling pressure
level, parameter
3022
must be set to the desired value
(see section 19);
2.- make sure no water leaks from the fittings;
3.- close the filling device provided for by the installer
upstream of the appliance;
4.- bleed the heating elements;
5.- check the pressure on the display again (part “M” in
figure 16-1). If it has gone down, fill the system to 1,5 bar
again (or up to the set value).
020014.01.010