10 - INSTALLATION - Hydraulic connections - boiler
10.1 - Boiler gas and
hydraulic connections
ATTENTION !!! Before installing, wash the
heating system and, if necessary, the domestic hot
water system thoroughly in order to remove any
residues or impurities that could compromise proper
appliance operation.
To identify the position of the fittings, see figures 8-1 and 8-2.
Gas connection
The gas connection must be done at the corresponding
fitting with a rigid metal pipe. The gas counter flow rate must
be sufficient for simultaneous use of all the gas appliances
connected to it. Connect the gas to the appliance according to
the standards in force. The diameter of the gas pipe coming
out of the generator does not determine the choice of the
diameter of the pipe between the appliance and the counter;
the latter must be chosen based on its length and head loss.
ATTENTION !!! Remember to install a gas shut-
off valve right before the appliance in order to be able
to shut off the gas supply.
ATTENTION !!! Supplying the boiler with
a different type of gas than those provided for is
prohibited.
10.2 - Boiler safety valve
(installer’s responsibility)
The appliance is supplied without an overpressure safety
valve to all the installer to choose the appropriate valve for
the system service pressure (check appliance operation
pressure in the technical features). Installation must be
done so as to allow the user to check valve intervention,
should it open. The safety valve drain (the installer’s
responsibility) must then be directed in order to avoid
danger for people in the event it intervenes.
ATTENTION !!! If the safety valve is not directed,
it could harm persons, animals or objects should it
intervene.
10.3 - Examples of boiler installations
Figure 10-1 - Example of boiler connection diagram
Figure 10-1 KEY
1 Boiler 60T-280T model boiler
2 INAIL safety valve
3 INAIL manometer
4 INAIL thermometer
5 INAIL maximum safety pressure switch
6 INAIL safety thermostat
7 Gas cock
8 INAIL gas shut-off valve
9 INAIL well
10 Gas inlet
11 Expansion tank
12 Micro-bubble separator
13 External probe
14 Filter
15 Electrical power supply
16 Low or high temperature heating system
17 System loading unit
18 Domestic cold water
19 Heating circuit pump
20 - Hydraulic separator
21 Air bleed valve
23 ----------
24 INAIL minimum safety pressure switch
36 Main circuit pump
37 Room thermostat or equivalent system
56 Balancing valve (necessary if there is a motorised valve,
part “17” in figure 3-1, on the appliance and the pump, “36”,
is
NOT
the modulating type)
57 Drain cock (Mandatory in the 60, 70, 100, 115, 140 models )
58 Manifold sensor