5
1
60T - 280T
COSMOGAS
Figure 15-7 - Label bearing the new adjustment
status of the appliance
Figure 15-8 - Settings for the various operating gases
15 - COMMISSIONING
U.M
60T
70T
100T
115T
140T
180T
210T
280T
Gas supply minimum pressure
mbar
10
Gas supply maximum pressure
mbar
45
Nozzle diameter for Methane gas (G20)
mm
8,9
9,5
8,9
8,9
9,5
9,5
9,5
Nozzle diameter for Methane gas (G25)
mm
N.P.
N.P.
N.P.
N.P.
N.P.
N.P.
N.P.
Nozzle diameter for LP gas (G31)
mm
6,2
6,5
6,2
6,2
6,5
6,5
6,5
Nozzle diameter for LP gas (G30)
mm
5,7
6,0
5,7
5,7
6,0
6,0
6,0
Methane gas CO2 (G20) at maximum output heat
%
from 8,4 to 9,0
Methane gas CO2 (G20) at minimum output heat
%
from 8,3 to 8,7
Methane gas O2 (G20) at maximum output heat
%
from 4,7 to 5,1
Methane gas O2 (G20) at minimum output heat
%
from 5,6 to 6,0
Methane gas CO (G20) at maximum and minimum output heat
ppm
Less than 150
Methane gas CO2 (G25) at maximum output heat
%
from 8,5 to 9,1
Methane gas CO2 (G25) at minimum output heat
%
from 8,1 to 8,5
Methane gas O2 (G25) at maximum output heat
%
from 4,7 to 5,1
Methane gas O2 (G25) at minimum output heat
%
from 5,6 to 6,0
Methane gas CO (G25) at maximum and minimum output heat
ppm
Less than 150
LP gas CO2 (G31) at maximum output heat
%
from 9,9 to 10,5
LP gas CO2 (G31) at minimum output heat
%
from 9,6 to 10,0
LP gas O2 (G31) at maximum output heat
%
from 5,2 to 5,6
LP gas O2 (G31) at minimum output heat
%
from 5,8 to 6,2
LP gas CO (G31) at maximum and minimum output heat
ppm
Less than 250
LP gas CO2 (G30) at maximum output heat
%
from 10,3 to 10,9
LP gas CO2 (G30) at minimum output heat
%
from 9,9 to 10,3
LP gas O2 (G30) at maximum output heat
%
from 4,9 to 5,3
LP gas O2 (G30) at minimum output heat
%
from 5,7 to 6,1
LP gas CO (G30) at maximum and minimum output heat
ppm
Less than 250