Outdoor Fixture High/Low Mount Sensor (continued)
Daylight Operation (closed loop)
•
Daylight operation is enabled by default.
•
When the measured light exceeds the calibrated level, the fixture will dim lighting to reduce
the light level.
•
When the measured light level exceeds 150% of the calibrated light level for more than 30
minutes, the sensor will dim to OFF.
•
Lighting will be turned back ON when one of the two conditions occurs:
•
The measured light level falls between 100% and 50% of the calibrated light level for
more than 10 minutes.
•
The measured light level falls below 50% of the calibrated light level for longer than 30
seconds.
Daylight Calibration Details
It is recommended that the daylight sensor be calibrated at night. During the day, there is too
much daylight to accurately calibrate.
During calibration, use the ‘Calibrate All’ feature and adjust slider bars to 100% to turn lighting
full ON. Once all fixtures are adjusted send the ‘Calibrate’ command.
Factory Reset Instructions
The factory reset will unprovision the device, setting the device back to factory settings. The
device will revert back to out-of-the-box behavior and will need to provisioned and
reprogrammed.
•
Cycle the power (switch OFF {1-4 seconds} and then ON {1-4 seconds}) to the device’s
circuit six times.
•
After a short period of time, the device should exhibit out-of-the-box behavior and may be
provisioned again.
Loss of Communications Operation
If a fixture mount sensor is no longer communicating with other sensors, it will operate with its
last programmed settings independently until communications are re-established.
Operation upon Return of Power
Upon return of power, the fixture will turn ON to the last known light level. If the fixture was OFF,
the power up will trigger the occupancy sensor to issue an occupied command. If occupancy set
is set for ‘Occupancy’ mode, the fixture will turn ON to the occupied light level until the sensor’s
hold time expires. If set for ‘Vacancy’ mode, the fixture will remain OFF if it was OFF prior to the
power loss.
Note:
It is recommended to avoid placing sensors within 3ft (1m) of air vents.