9. TROUBLE SHOOTING
Batcher does not reset.
The Signal Timeout has been set to an excessively long
period and has not timed out at the end of the last batch.
Batch will not start or relay 1 will not close.
Ensure that the instrument has not timed out as controlled
by the Signal Timeout and that a Flow Alarm condition
does not prevail. Pressing the Stop switch will cancel this
condition.
Check for a fault on the flow input before restarting.
Batcher stops midway through a batch.
This could be due to the Signal Timeout having timed
out.
Check for a fault in the system. Ensure that the Signal
Timeout period is significantly longer than the period
between pulses from the flowmeter at the minimum flowrate.
No display.
Check power to the instrument.
All 88888888 displayed.
The Batcher will display all eights on power up for 4 seconds
as a display test. If it continues to display all eights after this
period, this is symptomatic of the power supply voltage
being low. Check the power input voltage.
Trouble Shooting
75