414L-M-V3
Powering of Sensors
The Model 414L has a regulated DC output which can be used to power
sensors. A trimpot on the rear of the instrument allows the voltage to be
adjusted in the range of 8-24 Volts and the output can supply a maximum of
50mA.
Note that when using this DC output to power opto-sensors, some
flowmeter manufacturers require that a current limiting resistor be used.
Please refer to the flowmeter manufacturers data sheet if this is the
case.
Input Circuits