414L-M-V3
7.2 TEMPERATURE OR DENSITY INPUT
The Batch Controller can be supplied with either of two temperature
inputs:
* Direct 4 wire Platinum RTD (PT100)
Model 414LR
* 4-20mA Input for temperature or density
Model 414LA
RTD
Four wire RTD measurement is the most accurate form of measurement and
can be used for measurements with the RTD up to 100 meters from the
instrument. It is recommended to use shielded cable when interfacing to
RTD's.
Two or three wire RTD's can be used in place of 4 wire RTD's, but 4 wires
must e taken to the RTD and the signal and current wires joined as close to
the RTD as possible.
With the direct RTD measurement the program automatically corrects for
the non-linearity in the RTD.
68
Input Circuits
( + )
(-)
( + )
(-)
C u r r e n t
Sig nal
4
14
5
6
Shield
T w i s t e d
P a i r C a b l e
R T D
T emperature Sensor
Model 414LR
to case earth