BATCHING ON GROSS OR NET TOTAL (MASS)
The Batch Controller can be programmed to batch on either the Gross
Total (uncompensated) or the compensated Net Total or Mass Total.
Care should be taken when batching in Net or Mass units, so that a
vessel cannot be accidentally overfilled.
Note that the Gross Total is the total without temperature compensation
and the Net Total is the total after temperature compensation. Both totals
are reset on each batch.
DISPLAYED INFORMATION
The display will normally show the Batch Total, which is the total count for
the current batch. The Batch Total can be either the Gross, Net or Mass
depending on which value is programmed to control the batch.
The DISPLAY key can be used to display the following additional information:
Rate
On the first press of the DISPLAY key, the display shows RATE for
one second followed by the net flowrate (or MASS Flowrate).
Gross or Net Total
Since the batch can be controlled via the Gross or Net Total
(or MASS), the next value displayed on pressing the DISPLAY
key will depend on which value is used. If the batch is
controlled via the Gross Total, the Net Total (or MASS Total)
will be displayed. If the batch is controlled via the Net Total
(or MASS Total) the Gross Total will be displayed.