PLC Communication Settings
—
M2M Gateway PLC Communication Settings
—
52
—
6.
Ethernet Connection with KEYENCE PLC
The following is a setting example for Ethernet communication with the KEYENCE PLC KV-5000.
For communication with the KV-5000, the PLC communication protocol by Mitsubishi Electric (MC
protocol) is used.
* KEYENCE original communication protocol is not supported as of August 2018.
See below for the configuration example regarding communication conditions.
In this communication example, M2M Gateway setting is configured on the Mitsubishi device with
the Mitsubishi protocol.
Please check the KEYENCE manual for the compatibility between Mitsubishi devices and KEYENCE
devices.
An example with the KEYENCE PLC KV-5000 is listed below.
Device Name
KEYENCE device
Mitsubishi devices
Relay
R000 00 - R999 15
X(Y)0000 - X(Y)3E7F
Internal auxiliary relay
MR000 00 - MR999 15
M00000 - M15999
Latch relay
LR000 00 - LR999 15
L00000 - L15999
Data memory
DM00000 - DM65534
D00000 - D65534
Extended data memory
EM00000 - EM65534
D100000 - D165534
File register
FM00000 - FM32767
R00000 - R32767
ZF00000 - ZF131071
ZR00000 - ZR131071
M2M Gateway
PLC
KEYENCE KV-5000
IP address : 10.1.1.150
Subnet mask : 255.
0
.
0
.
0
Communication (Connection) port : 5100
* Ethernet port of the CPU Unit is used
IP address : 10.1.1.101
Subnet mask : 255.
0
.
0
.
0
Ethernet connection
MC protocol (Mitsubishi protocol)
Communication data cord : Binary
Device : DM1000 - DM1009
D1000-D1009 (Mitsubishi)
Access cycle : 1 sec
Device : LR10 00 - LR10 09
L160 - L169 (Mitsubishi)
Access cycle : 500 ms.