Fault Isolation
Condair GS
xxxxxxx_A_EN_1905_Condair-GS_OM
Code
Message
Probable Cause
Warning
Fault
W22
E22
Fill Warning
(W22)
Fill Timeout
(E22)
The fill valve(s) have been active for an extended length of time and the water level is
still zero. The dual fill valves remain activated.
The Fill Warning will eventually become a Fill Timeout if the issue has not been ad
-
dressed.
Water supply problems.
– Make sure that the water supply line is open, and there is adequate flow and pressure.
Loose wiring, or clogged strainer in dual fill valves.
– Check the wiring to the float board and the dual fill valves.
– Check the strainer in the dual fill valves is not clogged – refer to
Valves and Drain Pump" on page 54
Drain pump running, or manual drain valve open.
– Check that the manual drain valve is closed, and the drain pump is not running.
Floats may be stuck.
– Visually check that the different LEDs on the float board light up as the water level in
the float chamber changes. If necessary, clean the float chamber – refer to
.
Fill valve relay on the driver board not seated properly, or defective.
CAUTION!
Electro-static discharge damage to board.
– Check that LED3 (corresponding to REL4 for the high volume fill valve) and LED4
(corresponding to REL5 for the low volume fill valve) on the driver board light up when
the fill valves are supposed to be energized. If not, check the relay(s) is seated prop
-
erly on the driver board.
– Swap the relay(s) with another relay on the board to verify that it is working. If neces
-
sary, replace the relay.
Defective dual fill valves.
– Check for 24 VAC on the pins of the dual fill valves. If necessary, replace the dual fill
valves. Reconnect the wires correctly.
Scale build-up in the drain fitting.
– Clean the drain fitting, as described in
"Cleaning the Tank" on page 51
.
W28
E28
Maintenance
Due Warning
Maintenance
Due Fault (on
fault)
The preset service interval time has elapsed. The unit will continue to run for 200 hours
before a fault message is generated.
The unit will not operate if the warning message escalates to a fault message.
IMPORTANT!
Perform the required scheduled maintenance, then reset the service
reminder before restarting the unit.
Unit needs to be serviced.
–
Refer to
for maintenance procedures.
– Reset the service reminder after performing the required scheduled maintenance –
"Resetting Fault Status" on page 66
W32
–
RH Signal
The RH input is less than 3%. Operation is interrupted until an input higher than 3% is
received.
Loose wiring, faulty sensor.
– Check the connection between the sensor and the unit.
– Swap the sensor with another sensor and verify that it is working. If necessary, replace
the sensor.
Layout of the humidifier control system may be causing signal interference.
– Check that the controls layout permits accurate readings.
W34
–
Remote Disa-
bled
The unit has been disabled remotely by the building management system (BMS) through
Modbus communication. Operation is interrupted until the unit is enabled again through
Modbus or the control software.
Unit disabled by the BMS.
– Enable the unit through the BMS.
– If unit cannot be enabled remotely, try enabling the unit through the
setting in
the control software.
W35
–
BMS T/O (time
-
out)
The maximum wait time without any communications from the BMS has
is set to "Analog", the humidifier will
continue operating; otherwise it stops producing steam until communications with the
BMS is re-established.